AS/NZS 3000:2018
Table C5
Maximum demand for domestic cooking appliances
The circuit loading tool reads the assessed demand of a domestic cooking appliance from Table C5. The bands are set by the connected load in watts, and each band gives one demand current.
Verified: read against the printed standard, pages 477. Checked 26 Sept 2026.
Units: Max W W, Demand A A
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
5 rows
| Max W | Demand A |
|---|---|
| 5000 | 16 |
| 8000 | 20 |
| 10000 | 25 |
| 13000 | 32 |
| — | 40 |