Skip to content
AmpSize

AS/NZS 3000:2018

Table C5

Maximum demand for domestic cooking appliances

The circuit loading tool reads the assessed demand of a domestic cooking appliance from Table C5. The bands are set by the connected load in watts, and each band gives one demand current.

Verified: read against the printed standard, pages 477. Checked 26 Sept 2026.

Units: Max W W, Demand A A

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

5 rows

Table C5, Maximum demand for domestic cooking appliances
Max WDemand A
500016
800020
1000025
1300032
—40

Tools that read it (1)