AS/NZS 3000:2018

Table C4

Upstream circuit loading after diversity

The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.

Na-verify: binasa laban sa naka-print na standard, mga pahina 475. Na-check noong 26 Sept 2026.

Mga unit: Factor x

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3000:2018

4 na row

Table C4, Upstream circuit loading after diversity
MinMaxFactor (x)
230.9
450.8
690.7
10—0.6