AS/NZS 3000:2018
Table C4
Upstream circuit loading after diversity
The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.
Na-verify: binasa laban sa naka-print na standard, mga pahina 475. Na-check noong 26 Sept 2026.
Mga unit: Factor x
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
4 na row
| Min | Max | Factor (x) |
|---|---|---|
| 2 | 3 | 0.9 |
| 4 | 5 | 0.8 |
| 6 | 9 | 0.7 |
| 10 | — | 0.6 |