AS/NZS 3000:2018
Table C4
Upstream circuit loading after diversity
The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 475. I tirohia 26 Sept 2026.
Ngā unit: Factor x
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
4 rārangi
| Min | Max | Factor (x) |
|---|---|---|
| 2 | 3 | 0.9 |
| 4 | 5 | 0.8 |
| 6 | 9 | 0.7 |
| 10 | — | 0.6 |