跳至内容
AmpSize

AS/NZS 3000:2018

Table C4

Upstream circuit loading after diversity

The circuit loading tool reads the diversity factor that Table C4 allows on the circuit upstream of a group of final subcircuits. The factor falls as the number of devices downstream rises. The load schedule tool reads it for each board of a site.

已核验:对照印刷版标准阅读,页码 475。检查于 26 Sept 2026。

单位:Factor x

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

4 行

Table C4, Upstream circuit loading after diversity
MinMaxFactor (x)
230.9
450.8
690.7
10—0.6

读取它的工具 (2)

引用本内容的指南和学习页面 (4)