AS/NZS 3000:2018

Cl 5.5.3.2, 5.5.4.3

Screen, armour and sheath earthing

The screen and drain earthing tool reads the earthing point for each case, whether continuity is required, and the separation to use where a sheath may not be bonded to a pipe.

Verified: read against the printed standard, pages 177, 274, 295–296, 301, 306–307. Checked 27 Sept 2026.

Units: Separation mm mm, Insulation mm mm

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

6 rows

Cl 5.5.3.2, 5.5.4.3, Screen, armour and sheath earthing
CaseClauseEarth atContinuity requiredSeparation mmInsulation mm
cable-screen-required5.5.3.2(b)originyes——
wiring-enclosure5.5.3.2(a)originyes——
screen-as-protective-earth5.3.2.3(b)originyes——
screen-double-insulated5.5.3.2(b)not-requiredno——
earthing-not-required5.5.3.2(b)not-requiredno——
screen-near-flammable-pipe5.6.2.4bond—256