AS/NZS 3000:2018
Cl 5.5.3.2, 5.5.4.3
Screen, armour and sheath earthing
The screen and drain earthing tool reads the earthing point for each case, whether continuity is required, and the separation to use where a sheath may not be bonded to a pipe.
Đã xác minh: đối chiếu với tiêu chuẩn in, trang 177, 274, 295–296, 301, 306–307. Đã kiểm tra 27 Sept 2026.
Đơn vị: Separation mm mm, Insulation mm mm
Đây là các giá trị mà AmpSize mã hóa. Không sao chép nội dung tiêu chuẩn. Hãy đối chiếu với tiêu chuẩn hiện hành.
6 hàng
| Case | Clause | Earth at | Continuity required | Separation mm | Insulation mm |
|---|---|---|---|---|---|
| cable-screen-required | 5.5.3.2(b) | origin | yes | — | — |
| wiring-enclosure | 5.5.3.2(a) | origin | yes | — | — |
| screen-as-protective-earth | 5.3.2.3(b) | origin | yes | — | — |
| screen-double-insulated | 5.5.3.2(b) | not-required | no | — | — |
| earthing-not-required | 5.5.3.2(b) | not-required | no | — | — |
| screen-near-flammable-pipe | 5.6.2.4 | bond | — | 25 | 6 |