AS/NZS 3000:2018

Cl 5.5.3.2, 5.5.4.3

Screen, armour and sheath earthing

The screen and drain earthing tool reads the earthing point for each case, whether continuity is required, and the separation to use where a sheath may not be bonded to a pipe.

已核验:对照印刷版标准阅读,页码 177, 274, 295–296, 301, 306–307。检查于 27 Sept 2026。

单位:Separation mm mm, Insulation mm mm

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

6 行

Cl 5.5.3.2, 5.5.4.3, Screen, armour and sheath earthing
CaseClauseEarth atContinuity requiredSeparation mmInsulation mm
cable-screen-required5.5.3.2(b)originyes——
wiring-enclosure5.5.3.2(a)originyes——
screen-as-protective-earth5.3.2.3(b)originyes——
screen-double-insulated5.5.3.2(b)not-requiredno——
earthing-not-required5.5.3.2(b)not-requiredno——
screen-near-flammable-pipe5.6.2.4bond—256