The screen and drain earthing tool reads the earthing point for each case, whether continuity is required, and the separation to use where a sheath may not be bonded to a pipe.
已核验:对照印刷版标准阅读,页码 177, 274, 295–296, 301, 306–307。检查于 27 Sept 2026。
单位:Separation mm mm, Insulation mm mm
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
6 行
| Case | Clause | Earth at | Continuity required | Separation mm | Insulation mm |
|---|---|---|---|---|---|
| cable-screen-required | 5.5.3.2(b) | origin | yes | — | — |
| wiring-enclosure | 5.5.3.2(a) | origin | yes | — | — |
| screen-as-protective-earth | 5.3.2.3(b) | origin | yes | — | — |
| screen-double-insulated | 5.5.3.2(b) | not-required | no | — | — |
| earthing-not-required | 5.5.3.2(b) | not-required | no | — | — |
| screen-near-flammable-pipe | 5.6.2.4 | bond | — | 25 | 6 |