AS/NZS 3000:2018
Cl 5.5.3.2, 5.5.4.3
Screen, armour and sheath earthing
The screen and drain earthing tool reads the earthing point for each case, whether continuity is required, and the separation to use where a sheath may not be bonded to a pipe.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 177, 274, 295–296, 301, 306–307. I tirohia 27 Sept 2026.
Ngā unit: Separation mm mm, Insulation mm mm
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
6 rārangi
| Case | Clause | Earth at | Continuity required | Separation mm | Insulation mm |
|---|---|---|---|---|---|
| cable-screen-required | 5.5.3.2(b) | origin | yes | — | — |
| wiring-enclosure | 5.5.3.2(a) | origin | yes | — | — |
| screen-as-protective-earth | 5.3.2.3(b) | origin | yes | — | — |
| screen-double-insulated | 5.5.3.2(b) | not-required | no | — | — |
| earthing-not-required | 5.5.3.2(b) | not-required | no | — | — |
| screen-near-flammable-pipe | 5.6.2.4 | bond | — | 25 | 6 |