Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

حجم الموصل

4mm²

السعة بعد الخفض
29A
هبوط الجهد
3.05%
موصل الأرضي
2.5mm²
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Cable Size tool: conductor size 4 mm².

A 25 A single‑phase circuit takes 4 mm² copper cable on a typical New Zealand route. For 25 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 29 A of derated capacity and a voltage drop of 3.05 %.

Why not 2.5 mm²

On the same route, 2.5 mm² has 23 A of derated capacity. That is below the 25 A breaker, so the breaker would not protect the cable. Cl 2.5.3.1 sets that comparison: the device rating must not exceed the cable's capacity.

The case

The circuit runs at 230 V with a curve C breaker and a design current of 25 A. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.72 Ω.

Before you install

Grouping, a hot ceiling and thermal insulation all lower the capacity. Enter the real route and read the check the tool prints for each candidate size.

See also: What size breaker for 4 mm² cable and Ib, In and Iz.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
30 °C
الأسلاك الداخلية
متعدد القلوب
منحنى الجهاز
المنحنى C
تحقق من جهاز الحماية
نعم
الدوائر المجمّعة
1
العزل
PVC 75 °C
طول المسار
25 m
تيار التصميم
25 A
المادة
النحاس
طريقة التركيب
Enclosed in air
معامل القدرة
1
الأطوار
طور واحد
القيمة الاسمية للجهاز
25 A
حد هبوط الجهد
5 %
الجهد
230 V
المعاوقة الخارجية Ze
0.35 Ω