Tātaitai Transformer
Tātaitia te iahiko uta katoa me te impedance o te transformer.
Whakamātau mahi 5
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Check a transformer secondaryThe secondary current and the fault level of a 1000 kVA unit.
- Find the currents of a 500 kVA transformerThe primary and secondary currents of a 500 kVA unit.
- Find fault level of a 300 kVA unitThe secondary fault current at 4 % impedance.
- Check an isolating transformerThe currents of a 5 kVA single‑phase unit.
- Check a 22 kV transformerThe primary current of a 1500 kVA, 22 kV unit.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Reiti
- 500 kVA
- Ngā wāhanga
- Wāhanga toru
- Voltage tuatahi
- 11,000 V
- Whakahiato tuarua
- 400 V
- Impedance
- 6 %
Au utu katoa tuarua
721.69A
- Au utu katoa tuatahi
- 26.24A
- Au hapa tuarua
- 12,028.13A
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Au kawe kī katoa tuatahi26.24A
- Au kawe kī katoa tuaruaHua721.69A
- Au hapa tuarua12,028.13A
Mō tēnei tātaitai
How this is calculated
The tool gives the full load currents of a transformer and its secondary fault current. It uses the rating and the impedance from the nameplate.
- Inputs. You enter the rating in kVA and the number of phases. You also enter both voltages and the impedance in percent.
- Primary full load current. On three phases, I = kVA × 1000 ÷ (√3 × primary voltage). On one phase, it divides by the voltage alone.
- Secondary full load current. The tool applies the same formula at the secondary voltage.
- Secondary fault current. It divides the secondary full load current by the impedance as a fraction. For 6 %, that means dividing by 0.06.
The tool reads no table. You enter the voltages and the impedance.
Worked example
- 500 kVA, 11 kV to 400 V, 6 % impedance, three phase. The primary full load current is 26.24 A. The secondary full load current is 721.69 A. The secondary fault current is 12,028.13 A.
Limits
The fault current assumes an infinite upstream source. A real source has impedance, so the true fault current is lower. Use the fault level calculator to include the source. The tool does not model the cable after the transformer. It does not size the protection. Impedance is a nameplate value with a tolerance.
Use the primary current to check the supply side device. Use the secondary current to check the main switch and the busbar. Take the impedance from the nameplate, because it has a tolerance.
See also: Transformer full load current, 1000 kVA at 11 kV, Transformer secondary fault current, 500 kVA and Prospective fault current at a board.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He aha te mahi a te tātaitai transformer?
Ka whakaatu te taputapu i te primary Iahiko Uta Katoa, te secondary Iahiko Uta Katoa me te secondary iahiko hapa. Ka mahi mai i te rating i ngā kilovolt amperes, ngā voltage primary me secondary, te impedance percent me te maha o ngā wāhanga.
Ko ēhea ngā uruhanga e tino nui ana?
Ko te reiti me ngā voltage e rua e whakatau ana i ngā iahiko uta katoa e rua. Ko te ōrau impedance e whakatau ana i te iahiko hapa secondary: he iti iho te impedance, he nui ake te iahiko hapa. Ko te tatau wāhanga e whakamahi ana i te pūtakere o te toru ki ngā iahiko e rua.
He aha ngā raru noa?
Ka whakaaro te iahiko hapa he puna kore mutunga i runga, nō reira he tatauranga tino kino rawa, ā, ka kī te taputapu pēnei i ia putanga. Kāore i uru te impedance taura me te whatunga. Ka herea te impedance percent ki te 30. Ka noho ngā uruhanga ki te wāhitau o te whārangi, nō reira ka whakaputa tētahi hononga i te putanga.
Ngā tauira mahi
Kōrero o muri
- Short-circuit withstand and the k factorThe adiabatic check in plain terms: prospective fault current, clearing time and k, worked on 25 mm² copper XLPE at 10 kA for 0.1 s.
- Arc flash basicsArcing current, incident energy, boundary and working distance explained, with three engine runs that show clearing time beating fault current every time.
Ngā taputapu hononga
- Tātaitai rahi tauraFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Tātaitai taumata hapaProspective fault current at a board from its source.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Transformer inrush me tōna breakerCheck a transformer’s switch-on inrush against its breaker.AS/NZS 3000