Transformer calculator

Kalkulahin ang transformer full load current at impedance.

Walang standard

Mga input

Worked example gamit ang mga default na input.

Rating
500 kVA
Mga phase
Three phase
Primary voltage
11,000 V
Secondary voltage
400 V
Impedance
6 %

Secondary full load current

721.69A

Primary full load current
26.24A
Secondary fault current
12,028.13A

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Primary full load current26.24A
  2. Secondary full load currentResulta721.69A
  3. Secondary fault current12,028.13A

Tungkol sa calculator na ito

How this is calculated

The tool gives the full load currents of a transformer and its secondary fault current. It uses the rating and the impedance from the nameplate.

  1. Inputs. You enter the rating in kVA and the number of phases. You also enter both voltages and the impedance in percent.
  2. Primary full load current. On three phases, I = kVA × 1000 ÷ (√3 × primary voltage). On one phase, it divides by the voltage alone.
  3. Secondary full load current. The tool applies the same formula at the secondary voltage.
  4. Secondary fault current. It divides the secondary full load current by the impedance as a fraction. For 6 %, that means dividing by 0.06.

The tool reads no table. You enter the voltages and the impedance.

Worked example

Limits

The fault current assumes an infinite upstream source. A real source has impedance, so the true fault current is lower. Use the fault level calculator to include the source. The tool does not model the cable after the transformer. It does not size the protection. Impedance is a nameplate value with a tolerance.

Use the primary current to check the supply side device. Use the secondary current to check the main switch and the busbar. Take the impedance from the nameplate, because it has a tolerance.

See also: Transformer full load current, 1000 kVA at 11 kV, Transformer secondary fault current, 500 kVA and Prospective fault current at a board.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng transformer calculator?

Iniuulat ng tool ang primary full load current, secondary full load current at secondary fault current. Gumagana ito mula sa rating sa kilovolt amperes, sa primary at secondary voltage, sa impedance percent, at sa bilang ng phase.

Aling mga input ang pinakamahalaga?

Itinatakda ng rating at ng dalawang voltage ang dalawang full load current. Itinatakda ng impedance percent ang secondary fault current: mas mababang impedance, mas mataas na fault current. Ang bilang ng phase ang naglalapat ng square root ng tatlo sa parehong current.

Ano ang mga karaniwang gotcha?

Ipinapalagay ng fault current ang infinite na upstream source, kaya worst case figure ito at sinasabi iyon ng tool sa bawat resulta. Hindi kasama ang cable at network impedance. Limitado sa 30 ang impedance percent. Nasa page address ang mga input, kaya muling nagagawa ng link ang resulta.