RCD selection calculator

Check if an RCD is required and test the trip time.

Reads Electricity (Safety) Regulations 2010 and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Try a job 8

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Country
New Zealand
Installation
Residential
Final subcircuit
Socket-outlets
Circuit rating
20 A
Socket-outlet rating
10 A
Protection duty
Protection against electric shock
Rated residual current
30 mA
Check measured trip times
No

Additional RCD protection

Required

Rated residual current the clause requires
30mA
Maximum rated residual current for the duty
30mA
Limit at the rated residual current
300ms
Limit at five times rated
40ms
Maximum disconnection time
0.4s

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Additional protection requiredYes

    AS/NZS 3000:2018 Cl 2.6.3.3.1

  2. Rated residual current the clause requires30mA

    AS/NZS 3000:2018 Cl 2.6.3.3.1

  3. Maximum rated residual current for the duty30mA

    Electricity (Safety) Regulations 2010 reg 24

  4. Trip limit at the rated residual current300ms

    Electricity (Safety) Regulations 2010 reg 24

  5. Trip limit at five times the rated residual current40ms

    Electricity (Safety) Regulations 2010 reg 24

  6. Maximum disconnection time0.4s

    AS/NZS 3000:2018 Cl 5.7.2

  7. Must not trip at or below15mA

    Electricity (Safety) Regulations 2010 reg 24

About this calculator

How this is calculated

The tool says whether a circuit needs additional RCD protection. It picks the rated residual current. It can also test a measured trip time against the limits.

  1. Need. The tool reads the installation and the circuit type. It decides whether Clause 2.6.3.3.1 of AS/NZS 3000:2018 asks for additional protection.
  2. Rated current. It gives the rated residual current that the clause requires for that circuit.
  3. Maximum for the duty. In New Zealand you pick the duty: shock, property, patient or children. The tool gives the highest rated residual current for that duty (Electricity (Safety) Regulations 2010 reg 24).
  4. Trip limits. It gives the trip limit at the rated residual current. It also gives the limit at five times that current (reg 24).
  5. Disconnection time. It gives the maximum disconnection time (Cl 5.7.2).
  6. Measured result. If you enter two trip times, the tool compares them with the limits. It also gives the current below which the device must not trip.
StepTable or clauseWhat it decides
Need for protectionCl 2.6.3.3.1Whether the circuit needs an RCD
Rated current and trip limitsReg 24The rating and the trip times by duty
Disconnection timeCl 5.7.2The longest time to clear

Worked example

Limits

  • The tool does not choose a make or model. It does not check discrimination between RCDs.
  • It does not test nuisance tripping from earth leakage. A circuit with high leakage needs a site test.
  • The type of RCD (A, F or B) comes from the equipment on the circuit. See the learn page on RCD types.
  • The tool reads AS/NZS 3000:2018. Check the regulations for later changes.
  • Australia caps the circuit and New Zealand caps the socket-outlet in some cases. Check the hint on the form.

See also: RCD types and where they are required, Testing to Section 8 and Wet area zones.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the RCD selection tool do?

The tool reports whether the clauses it checks call for an RCD as additional protection on a final subcircuit. It gives the maximum rated residual current for the duty and the maximum trip times. It also checks measured trip times at the rated current and at five times that current against those limits.

Which clause and regulation does it use?

New Zealand circuits read AS/NZS 3000:2018 Clause 2.6.3.3, and Australian ones Clause 2.6.3.2.2 or Clause 2.6.3.2.3.3. A New Zealand electric vehicle circuit reads Clause 7.9.3 when domestic, and Clause 7.9.4 otherwise. A domestic Mode 2 circuit also takes the 30 mA of Clause 2.6.3.3.1. Trip limits come from Electricity (Safety) Regulations 2010 reg 24, and disconnection times from Clause 5.7.2.

What are the RCD trip time limits in New Zealand?

A shock protection RCD up to 30 mA has a 300 ms limit at its own rated residual current. At five times that current, its limit is 40 ms. Property protection takes an RCD rated up to 300 mA, with limits of 0.5 s and 0.15 s.

Why does a 40 amp circuit show no requirement?

In Australia, the tool reads Clause 2.6.3.2.3.3 outside a residential installation. That clause covers a final subcircuit rated 32 A or less, so above that the tool reports none. Clause 2.6.3.2.2 covers every final subcircuit of an Australian residential installation, at any rating. The New Zealand residential clause has no rating cap either.

Does the tool cover medical and patient areas?

Only in part. It reports regulation 24's 10 mA patient limits. It does not apply AS/NZS 3003, the patient areas standard. Read it for a medical location. The tool reads AS/NZS 3000 with Amendment 1. EV and Australian residential rows read the Amendment 1 to 3 compilation. Amendment 2 revised parts of Clause 2.6.3; check its current text.

Background

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.