Full load current calculator

Kalkulahin ang full load current mula sa power, voltage at phase.

Walang standard

Mga input

Worked example gamit ang mga default na input.

Mga phase
Three phase
Voltage
400 V
Yunit ng rating
kW
Rating
15
Power factor
0.9
Efficiency
1

Full load current

24.06A

Apparent power na nakuha
16.67kVA
Output power
15kW

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Output power15kW
  2. Apparent power na nakukuha16.67kVA
  3. Full load currentResulta24.06A

Tungkol sa calculator na ito

How this is calculated

The tool works out the full load current of a load. It uses the power, the voltage, the power factor and the efficiency. It works on one phase or three. It reads no table, so it cites no clause.

  1. Supply. You pick one phase or three and enter the voltage. The voltage you enter sets the divisor in the last step.
  2. Output power. You enter the load in kW or kVA. For a kW load, the tool takes this as the output power.
  3. Apparent power drawn. It divides the output power by the efficiency and by the power factor. A kVA entry skips the power factor step.
  4. Full load current. On one phase, it divides the apparent power by the voltage. On three phases, it divides by the voltage and by the square root of three.

On three phases, enter the line voltage, such as 400 V. On one phase, enter the phase voltage, such as 230 V.

Worked example

Limits

The result is the steady running current. It is not the starting current. A motor draws more current at start. Use the motor tool for the starting current.

The tool assumes a balanced load on three phases. It does not add a margin for the cable or the breaker. Size the cable from the design current with the cable size calculator. The tool gives no harmonic or neutral current.

Efficiency is a value between 0 and 1. A kVA entry is already an apparent power, so the tool does not divide it by the power factor.

Check the efficiency you enter. A motor rating in kW is a shaft output, so enter the motor efficiency. A resistive heater has an efficiency of 1. Check the power factor on the nameplate. A low power factor raises the current for the same kW.

See also: Commercial kitchen kW to amps, Three‑phase power kVA to amps at 400 V and the three‑phase power tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng full load current calculator?

Kino-convert ng tool ang load rating tungo sa current. Ilagay ang rating sa kilowatts o kilovolt amperes, ang voltage at ang bilang ng phase. Iniuulat nito ang full load current ng load, ang real power nito at ang apparent power nito.

Aling mga input ang pinakamahalaga?

Itinatakda ng rating at ng voltage ang current. Para sa kilowatt rating, parehong nagpapataas ng apparent power ang power factor at efficiency, kaya parehong nagpapataas ng current. Para sa kilovolt ampere rating, hindi inilalapat ang efficiency. Ang three phase na resulta ay hinahati sa square root ng tatlo.

Ano ang hindi ginagawa ng tool na ito?

Hindi ito nagsi-size ng cable o protective device. Walang binabanggit na standard table, dahil direktang kalkulasyon ang resulta. Gamitin ang current na ibinibigay nito bilang design current sa cable size tool. Nasa page address ang mga input, kaya inuulit ng link ang resulta.