AmpSize

Tātaitai Iahiko Uta Katoa

Tātaitia te iahiko uta katoa mai i te mana, te voltage me te wāhanga.

Kāore he paerewa

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Ngā wāhanga
Wāhanga toru
Voltage
400 V
Wae whakatauhanga
kW
Reiti
15
Power factor
0.9
Pai
1

Iahiko Uta Katoa

24.06A

Pūngao ariā kukumea
16.67kVA
Pūngao putanga
15kW

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Hiko puta15kW
  2. Pūngao ariā kukumea16.67kVA
  3. Au utanga katoaHua24.06A

Mō tēnei tātaitai

How this is calculated

The tool works out the full load current of a load. It uses the power, the voltage, the power factor and the efficiency. It works on one phase or three. It reads no table, so it cites no clause.

  1. Supply. You pick one phase or three and enter the voltage. The voltage you enter sets the divisor in the last step.
  2. Output power. You enter the load in kW or kVA. For a kW load, the tool takes this as the output power.
  3. Apparent power drawn. It divides the output power by the efficiency and by the power factor. A kVA entry skips the power factor step.
  4. Full load current. On one phase, it divides the apparent power by the voltage. On three phases, it divides by the voltage and by the square root of three.

On three phases, enter the line voltage, such as 400 V. On one phase, enter the phase voltage, such as 230 V.

Worked example

Limits

The result is the steady running current. It is not the starting current. A motor draws more current at start. Use the motor tool for the starting current.

The tool assumes a balanced load on three phases. It does not add a margin for the cable or the breaker. Size the cable from the design current with the cable size calculator. The tool gives no harmonic or neutral current.

Efficiency is a value between 0 and 1. A kVA entry is already an apparent power, so the tool does not divide it by the power factor.

Check the efficiency you enter. A motor rating in kW is a shaft output, so enter the motor efficiency. A resistive heater has an efficiency of 1. Check the power factor on the nameplate. A low power factor raises the current for the same kW.

See also: Commercial kitchen kW to amps, Three‑phase power kVA to amps at 400 V and the three‑phase power tool.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He aha te mahi a te tātaitai iahiko uta katoa?

Ka hurihia e te taputapu te reiti uta ki tētahi iahiko. Uruhia te reiti ki ngā kilowatt, ki ngā kilovolt amperes rānei, te voltage me te tatau wāhanga. Ka pūrongo i te iahiko uta katoa o te uta, tōna real power me tōna apparent power.

Ko ēhea ngā uruhanga e tino nui ana?

Ko te reiti me te voltage e whakatau ana i te iahiko. Mō tētahi reiti kilowatt, ko te power factor me te efficiency e whakatairanga ana i te apparent power, nō reira e whakatairanga ana i te iahiko. Mō tētahi reiti kilovolt ampere kāore te efficiency e whakamahia. Ko te putanga wāhanga toru ka whakawehea ki te pūtakere o te toru.

He aha ngā mea kāore e mahia e tēnei taputapu?

Kāore e rahi i tētahi taura, i tētahi taputapu whakamaru. Kāore he tūtohi paerewa e tohua ana, nō te mea he tātaitanga tōtika te putanga. Whakamahia te iahiko e hoatu ana e ia hei iahiko hoahoa i te taputapu Rahi Taura. Ka noho ngā uruhanga ki te wāhitau o te whārangi, nō reira ka whakaputa tētahi hononga i te putanga.

Ngā tauira mahi

Kōrero o muri

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.