Battery location checker
Check where a home battery can go under AS/NZS 5139.
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
Try a job 4
Each job fills in example values. Replace them with your values.
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
Inputs
Worked example with the default inputs. The live calculator replaces it when the page loads.
- Battery type
- All-in-one (pre-assembled integrated BESS)
- Location
- Garage
- Battery IP code
- IP55
- Distance to the nearest exit
- 1,500 mm
- Distance to a window or vent
- 0 mm
- Distance to an appliance
- 800 mm
- An exit, window or appliance above it
- No
- On a wall to a habitable room
- No
- Gap to the ceiling
- 1,100 mm
- The building has a fire indication panel
- No
- Working space in front
- 1,000 mm
- Panels reach the 230 V a.c. connections
- Yes
- Maker’s clearance
- 0 mm
AS/NZS 5139 Section 4
8 of 9 rules met
- Rules met
- 8
- Rules not met
- 0
- Not assessed
- 1
This result is a design aid. Verify it against the current standard.
Calculation steps
- Clearance to an exit, a window or vent, or an appliance, at least600mm
AS/NZS 5139:2019 Cl 4.2.2.2
- Clear below those items, at least900mm
AS/NZS 5139:2019 Cl 4.2.2.2(e)
- IP code indoors, at leastIP2X
AS/NZS 5139:2019 Cl 4.2.3.2
- Working space, at least900mm
AS/NZS 5139:2019 Cl 4.2.5
About this calculator
How this is calculated
The tool checks a site for an all-in-one home battery. It reads AS/NZS 5139:2019 Section 4. It shows each rule as met, not met or not assessed. A distance you leave blank stays not assessed.
- Place. It tests the location against the restricted places (Cl 4.2.2.2(a) to (k)). These are switchboard-restricted places, ceiling spaces, wall cavities, roofs unless deemed suitable, under stairways or access walkways, and escape routes. They also include habitable rooms of homes and hazardous areas.
- Clearances. It compares your distances to an exit, a window or vent of a habitable room, and another appliance with the 600 mm rule. An item above the battery needs the 900 mm rule. In a corridor it checks the 1 m left for egress (Cl 4.2.2.1).
- IP code. It wants IP2X indoors and IP23 outdoors (Cl 4.2.3.2). It compares each digit of your code.
- Barrier. If the battery is on a wall to a habitable room, the wall must be non-combustible (Cl 4.2.4.2). On a combustible wall, a non-combustible barrier must reach 600 mm past each side, 900 mm above and down to the bottom.
- Ceiling. If the ceiling is within 900 mm of the top, it must be non-combustible for 600 mm past the battery (Cl 4.2.4.2).
- Working space. It wants 600 mm on the working side, or 900 mm where panels reach the 230 V a.c. connections. It takes the maker's figure if that is larger (Cl 4.2.5).
- Notes. It adds notes for a smoke alarm or fire panel detector (Cl 4.3.4, a "should") and for the maker's ventilation instructions (Cl 4.3.5).
| Check | Clause | What it decides |
|---|---|---|
| Location | Cl 4.2.2.2 | Whether the place is restricted |
| Exit, window, appliance | Cl 4.2.2.2 | The side and below clearances |
| Corridor | Cl 4.2.2.1 | The width left for egress |
| IP rating | Cl 4.2.3.2 | The least enclosure rating |
| Barrier | Cl 4.2.4.2 | The non-combustible wall behind the battery |
| Ceiling | Cl 4.2.4.2 | The non-combustible ceiling above it |
| Working space | Cl 4.2.5 | The clear space to work in |
Worked example
- A garage wall that backs onto a bedroom. The tool gives 4 of 9 rules not met: the appliance clearance, the barrier, the ceiling and the working space. The hot water unit is 400 mm away. The barrier reaches 300 mm each side and 500 mm above. The ceiling is 700 mm over the battery. The working space is 700 mm.
- The same wall, fixed. The tool gives 9 of 9 rules met.
Limits
- The tool covers a pre-assembled integrated BESS, Section 4. It does not assess other battery types. AmpSize does not hold Sections 5 and 6.
- AmpSize does not hold Amendment 1 (2025). Check it for changes.
- The tool tests the numbers you enter. It does not know your site. A roof needs a check that it is deemed suitable.
- It does not size the battery, the cable or the protection.
See also: Home battery location and clearances, Where can a home battery go, Solar battery size for a family home and the home battery tool.
Questions
Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.
Where can a home battery not go?
AS/NZS 5139:2019 Cl 4.2.2.2 keeps an all-in-one battery out of habitable rooms, ceiling spaces, wall cavities, the space under stairs or walkways, escape routes and hazardous areas. A roof is allowed only where it is deemed suitable.
How far must a battery be from a door, window or hot water unit?
At least 600 mm to the side of an exit, a window or vent of a habitable room, or another appliance such as a hot water unit or air conditioner. It must also sit at least 900 mm below any of them.
Can a battery go on a wall to a bedroom?
Yes, if the wall is non-combustible, such as brick, concrete, cement sheet or tiles. On a combustible wall, fit a non-combustible barrier 600 mm past each side and 900 mm above. A ceiling within 900 mm needs the same.
How much space does a battery need in front of it?
At least 600 mm on the working side, or 900 mm where the panels reach the 230 V a.c. connections. Where the maker asks for more, the tool takes the larger figure.
Does the tool cover every battery?
It covers the all-in-one home battery, Section 4 of AS/NZS 5139. AmpSize does not hold the Section 5 and 6 rules for other systems, or Amendment 1 (2025). The tool says so rather than guess.
Clauses and tables this tool reads
- AS/NZS 5139:2019 Cl 4.2.2.2Restricted locations for a home battery
- AS/NZS 5139:2019 Cl 4.2.3.1Battery location by risk assessment
- AS/NZS 5139:2019 Cl 4.2.3.2IP rating of a home battery
- AS/NZS 5139:2019 Cl 4.2.4.2Barrier to a habitable room
- AS/NZS 5139:2019 Cl 4.2.5Working space at a home battery
- AS/NZS 5139:2019 Cl 4.3.4Smoke alarm or detector at a home battery
- AS/NZS 5139:2019 Cl 4.3.5Ventilation of a home battery
- AS/NZS 5139:2019 Cl 4.2.2 to 4.2.5Location, clearance and barrier rules for a pre-assembled integrated BESS
Every clause and table, with how each was verified
Tables last checked on 1 Oct 2026.