أداة فحص موقع البطارية
تحقّق من مكان وضع البطارية المنزلية وفق AS/NZS 5139.
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
جرّب مشروعاً 4
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- نوع البطارية
- الكل في واحد (BESS متكامل مُجمَّع مسبقًا)
- الموقع
- الجراج
- رمز IP للبطارية
- IP55
- Distance to the nearest exit
- 1,500 mm
- Distance to a window or vent
- 0 mm
- Distance to an appliance
- 800 mm
- مخرج أو نافذة أو جهاز فوقه
- لا
- على جدار يفضي إلى غرفة صالحة للسكن
- لا
- Gap to the ceiling
- 1,100 mm
- يوجد في المبنى لوحة إنذار حريق
- لا
- Working space in front
- 1,000 mm
- اللوحات تصل إلى وصلات 230 V تيار متردد
- نعم
- Maker’s clearance
- 0 mm
القسم 4 من AS/NZS 5139
8 من 9 قاعدة مستوفاة
- القواعد المستوفاة
- 8
- القواعد غير المستوفاة
- 0
- لم يُقيَّم
- 1
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- الخلوص من مخرج أو نافذة أو فتحة تهوية أو جهاز، بحد أدنى600mm
AS/NZS 5139:2019 Cl 4.2.2.2
- خلوص أسفل تلك العناصر، بحد أدنى900mm
AS/NZS 5139:2019 Cl 4.2.2.2(e)
- رمز IP داخلياً، بحد أدنىIP2X
AS/NZS 5139:2019 Cl 4.2.3.2
- مساحة العمل، على الأقل900mm
AS/NZS 5139:2019 Cl 4.2.5
حول هذه الحاسبة
How this is calculated
The tool checks a site for an all-in-one home battery. It reads AS/NZS 5139:2019 Section 4. It shows each rule as met, not met or not assessed. A distance you leave blank stays not assessed.
- Place. It tests the location against the restricted places (Cl 4.2.2.2(a) to (k)). These are switchboard-restricted places, ceiling spaces, wall cavities, roofs unless deemed suitable, under stairways or access walkways, and escape routes. They also include habitable rooms of homes and hazardous areas.
- Clearances. It compares your distances to an exit, a window or vent of a habitable room, and another appliance with the 600 mm rule. An item above the battery needs the 900 mm rule. In a corridor it checks the 1 m left for egress (Cl 4.2.2.1).
- IP code. It wants IP2X indoors and IP23 outdoors (Cl 4.2.3.2). It compares each digit of your code.
- Barrier. If the battery is on a wall to a habitable room, the wall must be non‑combustible (Cl 4.2.4.2). On a combustible wall, a non‑combustible barrier must reach 600 mm past each side, 900 mm above and down to the bottom.
- Ceiling. If the ceiling is within 900 mm of the top, it must be non‑combustible for 600 mm past the battery (Cl 4.2.4.2).
- Working space. It wants 600 mm on the working side, or 900 mm where panels reach the 230 V a.c. connections. It takes the maker's figure if that is larger (Cl 4.2.5).
- Notes. It adds notes for a smoke alarm or fire panel detector (Cl 4.3.4, a "should") and for the maker's ventilation instructions (Cl 4.3.5).
| Check | Clause | What it decides |
|---|---|---|
| Location | Cl 4.2.2.2 | Whether the place is restricted |
| Exit, window, appliance | Cl 4.2.2.2 | The side and below clearances |
| Corridor | Cl 4.2.2.1 | The width left for egress |
| IP rating | Cl 4.2.3.2 | The least enclosure rating |
| Barrier | Cl 4.2.4.2 | The non‑combustible wall behind the battery |
| Ceiling | Cl 4.2.4.2 | The non‑combustible ceiling above it |
| Working space | Cl 4.2.5 | The clear space to work in |
Worked example
- A garage wall that backs onto a bedroom. The tool gives 4 of 9 rules not met: the appliance clearance, the barrier, the ceiling and the working space. The hot water unit is 400 mm away. The barrier reaches 300 mm each side and 500 mm above. The ceiling is 700 mm over the battery. The working space is 700 mm.
- The same wall, fixed. The tool gives 9 of 9 rules met.
Limits
- The tool covers a pre-assembled integrated BESS, Section 4. It does not assess other battery types. AmpSize does not hold Sections 5 and 6.
- AmpSize does not hold Amendment 1 (2025). Check it for changes.
- The tool tests the numbers you enter. It does not know your site. A roof needs a check that it is deemed suitable.
- It does not size the battery, the cable or the protection.
See also: Home battery location and clearances, Where can a home battery go, Solar battery size for a family home and the home battery tool.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
أين لا يمكن وضع البطارية المنزلية؟
يُبعد AS/NZS 5139:2019 Cl 4.2.2.2 البطارية المنزلية المتكاملة عن الغرف المأهولة، ومساحات الأسقف، وتجاويف الجدران، والمساحة تحت الدرج أو الممرات، ومسارات الهروب، والمناطق الخطرة. ولا يُسمح بالسقف إلا حيث يُعتبر مناسباً.
كم يجب أن تبعد البطارية عن الباب أو النافذة أو وحدة الماء الساخن؟
على الأقل 600 mm جانبياً عن مخرج، أو نافذة أو فتحة تهوية لغرفة مأهولة، أو جهاز آخر مثل وحدة الماء الساخن أو مكيف الهواء. ويجب أيضاً أن يكون على بُعد 900 mm على الأقل أسفل أيٍّ منها.
هل يمكن تثبيت بطارية على جدار ملاصق لغرفة نوم؟
نعم، إذا كان الجدار غير قابل للاشتعال، مثل الطوب أو الخرسانة أو ألواح الأسمنت أو البلاط. وعلى جدار قابل للاشتعال، ركّب حاجزًا غير قابل للاشتعال بامتداد 600 mm بعد كل جانب و900 mm فوق. ويحتاج السقف الذي يقع ضمن 900 mm إلى الشيء نفسه.
كم من المساحة تحتاجها البطارية أمامها؟
على الأقل 600 mm من جهة العمل، أو 900 mm حيث تصل الألواح إلى توصيلات 230 V a.c. عندما يطلب الصانع أكثر من ذلك، تأخذ الأداة الرقم الأكبر.
هل تغطي الأداة كل بطارية؟
تغطي البطارية المنزلية المتكاملة، Section 4 من AS/NZS 5139. لا يتضمن AmpSize قواعد Section 5 وSection 6 للأنظمة الأخرى، ولا Amendment 1 (2025). وتذكر الأداة ذلك بدلاً من التخمين.
أمثلة محلولة
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 5139:2019 Cl 4.2.2.2Restricted locations for a home battery
- AS/NZS 5139:2019 Cl 4.2.3.1Battery location by risk assessment
- AS/NZS 5139:2019 Cl 4.2.3.2IP rating of a home battery
- AS/NZS 5139:2019 Cl 4.2.4.2Barrier to a habitable room
- AS/NZS 5139:2019 Cl 4.2.5Working space at a home battery
- AS/NZS 5139:2019 Cl 4.3.4Smoke alarm or detector at a home battery
- AS/NZS 5139:2019 Cl 4.3.5Ventilation of a home battery
- AS/NZS 5139:2019 Cl 4.2.2 to 4.2.5Location, clearance and barrier rules for a pre-assembled integrated BESS
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 1 Oct 2026.