बैटरी लोकेशन चेकर
AS/NZS 5139 के तहत जाँचें कि होम बैटरी कहाँ लग सकती है।
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- बैटरी का प्रकार
- ऑल-इन-वन (पहले से असेंबल्ड इंटीग्रेटेड BESS)
- स्थान
- गैराज
- बैटरी IP कोड
- IP55
- Distance to the nearest exit
- 1,500 mm
- Distance to a window or vent
- 0 mm
- Distance to an appliance
- 800 mm
- इसके ऊपर कोई निकास, खिड़की या उपकरण
- नहीं
- रहने योग्य कमरे की दीवार पर
- नहीं
- Gap to the ceiling
- 1,100 mm
- भवन में फ़ायर इंडिकेशन पैनल है
- नहीं
- Working space in front
- 1,000 mm
- पैनल 230 V a.c. कनेक्शन तक पहुँचते हैं
- हाँ
- Maker’s clearance
- 0 mm
AS/NZS 5139 Section 4
9 में से 8 नियम पूरे हुए
- नियम पूरे हुए
- 8
- नियम पूरे नहीं हुए
- 0
- मूल्यांकन नहीं हुआ
- 1
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- किसी एग्ज़िट, खिड़की या वेंट, या उपकरण तक क्लियरेंस, कम से कम600mm
AS/NZS 5139:2019 Cl 4.2.2.2
- उन आइटमों के नीचे कम से कम इतनी जगह छोड़ें900mm
AS/NZS 5139:2019 Cl 4.2.2.2(e)
- घर के भीतर IP कोड, कम से कमIP2X
AS/NZS 5139:2019 Cl 4.2.3.2
- कार्य स्थान, कम से कम900mm
AS/NZS 5139:2019 Cl 4.2.5
इस कैलकुलेटर के बारे में
How this is calculated
The tool checks a site for an all-in-one home battery. It reads AS/NZS 5139:2019 Section 4. It shows each rule as met, not met or not assessed. A distance you leave blank stays not assessed.
- Place. It tests the location against the restricted places (Cl 4.2.2.2(a) to (k)). These are switchboard-restricted places, ceiling spaces, wall cavities, roofs unless deemed suitable, under stairways or access walkways, and escape routes. They also include habitable rooms of homes and hazardous areas.
- Clearances. It compares your distances to an exit, a window or vent of a habitable room, and another appliance with the 600 mm rule. An item above the battery needs the 900 mm rule. In a corridor it checks the 1 m left for egress (Cl 4.2.2.1).
- IP code. It wants IP2X indoors and IP23 outdoors (Cl 4.2.3.2). It compares each digit of your code.
- Barrier. If the battery is on a wall to a habitable room, the wall must be non‑combustible (Cl 4.2.4.2). On a combustible wall, a non‑combustible barrier must reach 600 mm past each side, 900 mm above and down to the bottom.
- Ceiling. If the ceiling is within 900 mm of the top, it must be non‑combustible for 600 mm past the battery (Cl 4.2.4.2).
- Working space. It wants 600 mm on the working side, or 900 mm where panels reach the 230 V a.c. connections. It takes the maker's figure if that is larger (Cl 4.2.5).
- Notes. It adds notes for a smoke alarm or fire panel detector (Cl 4.3.4, a "should") and for the maker's ventilation instructions (Cl 4.3.5).
| Check | Clause | What it decides |
|---|---|---|
| Location | Cl 4.2.2.2 | Whether the place is restricted |
| Exit, window, appliance | Cl 4.2.2.2 | The side and below clearances |
| Corridor | Cl 4.2.2.1 | The width left for egress |
| IP rating | Cl 4.2.3.2 | The least enclosure rating |
| Barrier | Cl 4.2.4.2 | The non‑combustible wall behind the battery |
| Ceiling | Cl 4.2.4.2 | The non‑combustible ceiling above it |
| Working space | Cl 4.2.5 | The clear space to work in |
Worked example
- A garage wall that backs onto a bedroom. The tool gives 4 of 9 rules not met: the appliance clearance, the barrier, the ceiling and the working space. The hot water unit is 400 mm away. The barrier reaches 300 mm each side and 500 mm above. The ceiling is 700 mm over the battery. The working space is 700 mm.
- The same wall, fixed. The tool gives 9 of 9 rules met.
Limits
- The tool covers a pre-assembled integrated BESS, Section 4. It does not assess other battery types. AmpSize does not hold Sections 5 and 6.
- AmpSize does not hold Amendment 1 (2025). Check it for changes.
- The tool tests the numbers you enter. It does not know your site. A roof needs a check that it is deemed suitable.
- It does not size the battery, the cable or the protection.
See also: Home battery location and clearances, Where can a home battery go, Solar battery size for a family home and the home battery tool.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
होम बैटरी कहाँ नहीं लग सकती?
AS/NZS 5139:2019 Cl 4.2.2.2 ऑल-इन-वन बैटरी को रहने योग्य कमरों, सीलिंग स्पेस, दीवार की खोखली जगहों, सीढ़ियों या वॉकवे के नीचे की जगह, एस्केप रूट और खतरनाक एरिया से बाहर रखता है। छत केवल तभी अनुमत है जहाँ उसे उपयुक्त माना गया हो।
बैटरी दरवाज़े, खिड़की या गर्म पानी की यूनिट से कितनी दूर होनी चाहिए?
निकास के, रहने योग्य कमरे की खिड़की या वेंट के, या गर्म पानी की यूनिट या एयर कंडीशनर जैसे किसी अन्य उपकरण के किनारे से कम से कम 600 mm। इसे इनमें से किसी के भी नीचे कम से कम 900 mm पर होना चाहिए।
क्या बैटरी बेडरूम की दीवार पर लगाई जा सकती है?
हाँ, अगर दीवार नॉन-कम्बस्टिबल है, जैसे ईंट, कंक्रीट, सीमेंट शीट या टाइल। कम्बस्टिबल दीवार पर, हर किनारे से 600 mm आगे और 900 mm ऊपर तक नॉन-कम्बस्टिबल बैरियर लगाएँ। 900 mm के भीतर की छत को भी यही चाहिए।
बैटरी के सामने कितनी जगह चाहिए?
वर्किंग साइड पर कम से कम 600 mm, या जहाँ पैनल 230 V a.c. कनेक्शन तक पहुँचते हैं वहाँ 900 mm। जहाँ निर्माता ज़्यादा माँगे, टूल बड़ा आंकड़ा लेता है।
क्या टूल हर बैटरी को कवर करता है?
यह ऑल-इन-वन होम बैटरी को कवर करता है, AS/NZS 5139 का Section 4। AmpSize के पास अन्य सिस्टम के लिए Section 5 और 6 के नियम नहीं हैं, न ही Amendment 1 (2025)। टूल अनुमान लगाने के बजाय यह साफ़ बताता है।
हल किए गए उदाहरण
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 5139:2019 Cl 4.2.2.2Restricted locations for a home battery
- AS/NZS 5139:2019 Cl 4.2.3.1Battery location by risk assessment
- AS/NZS 5139:2019 Cl 4.2.3.2IP rating of a home battery
- AS/NZS 5139:2019 Cl 4.2.4.2Barrier to a habitable room
- AS/NZS 5139:2019 Cl 4.2.5Working space at a home battery
- AS/NZS 5139:2019 Cl 4.3.4Smoke alarm or detector at a home battery
- AS/NZS 5139:2019 Cl 4.3.5Ventilation of a home battery
- AS/NZS 5139:2019 Cl 4.2.2 to 4.2.5Location, clearance and barrier rules for a pre-assembled integrated BESS
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 1 Oct 2026 को जाँची गईं।
संबंधित टूल
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।