NZS 4512:2010

Cl 402

Fire alarm cable and circuit requirements

The fire alarm cabling tool reads one row per circuit type. Each row holds the smallest conductor size for two cores and for more than two, and the stranding threshold. It also holds the insulation resistance criterion, the AS/NZS 3013 fire rating and integrity time, and the supply subcircuit label. A null size means Clause 402.1 sets none for that circuit.

Verified: read against the printed standard, pages 44–45. Checked 26 Sept 2026.

Units: Size mm2, Insulation resistance MOhm, Fire rating minutes min

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the NZS 4512:2010 page

6 rows

Cl 402, Fire alarm cable and circuit requirements
CircuitTwo core min mm 2Multi core min mm 2Fire ratingFire rating minutes (min)Dedicated circuitLabelClause
detector0.750.5——no—402.1
alerting-device0.750.5——no—402.1
transmission——AS/NZS 3013 WS1115no—402.2(m)
staged-evacuation0.750.5AS/NZS 3013 WS51W—no—402.2(r)
data-link————no—402.2(q)
mains-supply————yesFIRE ALARM402.2(f)