NZS 4512:2010
Cl 402
Fire alarm cable and circuit requirements
The fire alarm cabling tool reads one row per circuit type. Each row holds the smallest conductor size for two cores and for more than two, and the stranding threshold. It also holds the insulation resistance criterion, the AS/NZS 3013 fire rating and integrity time, and the supply subcircuit label. A null size means Clause 402.1 sets none for that circuit.
Na-verify: binasa laban sa naka-print na standard, mga pahina 44–45. Na-check noong 26 Sept 2026.
Mga unit: Size mm2, Insulation resistance MOhm, Fire rating minutes min
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
6 na row
| Circuit | Two core min mm 2 | Multi core min mm 2 | Fire rating | Fire rating minutes (min) | Dedicated circuit | Label | Clause |
|---|---|---|---|---|---|---|---|
| detector | 0.75 | 0.5 | — | — | no | — | 402.1 |
| alerting-device | 0.75 | 0.5 | — | — | no | — | 402.1 |
| transmission | — | — | AS/NZS 3013 WS11 | 15 | no | — | 402.2(m) |
| staged-evacuation | 0.75 | 0.5 | AS/NZS 3013 WS51W | — | no | — | 402.2(r) |
| data-link | — | — | — | — | no | — | 402.2(q) |
| mains-supply | — | — | — | — | yes | FIRE ALARM | 402.2(f) |