Fire alarm cable and circuit requirements

The fire alarm cabling tool reads one row per circuit type. Each row holds the smallest conductor size for two cores and for more than two, and the stranding threshold. It also holds the insulation resistance criterion, the AS/NZS 3013 fire rating and integrity time, and the supply subcircuit label. A null size means Clause 402.1 sets none for that circuit.

已核验:对照印刷版标准阅读,页码 44–45。检查于 26 Sept 2026。

单位:Size mm2, Insulation resistance MOhm, Fire rating minutes min

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 NZS 4512:2010 页面上的对应卡片

6 行

Cl 402, Fire alarm cable and circuit requirements
CircuitTwo core min mm 2Multi core min mm 2Fire ratingFire rating minutes (min)Dedicated circuitLabelClause
detector0.750.5——no—402.1
alerting-device0.750.5——no—402.1
transmission——AS/NZS 3013 WS1115no—402.2(m)
staged-evacuation0.750.5AS/NZS 3013 WS51W—no—402.2(r)
data-link————no—402.2(q)
mains-supply————yesFIRE ALARM402.2(f)