AS/NZS 3760:2022
Table 2.4
Indicative testing and inspection intervals for electrical equipment
The test and tag tool reads the retest interval for each of the eight environments of Table 2.4, for the equipment itself and for the push-button and operating time tests of a portable or fixed RCD. A row says which of its cells the table prints as not applicable.
Na-verify: binasa laban sa naka-print na standard, mga pahina 21–23 (PDF 25–27). Na-check noong 1 Oct 2026.
Mga unit: Equipment months months, Rcd push portable months months, Rcd push fixed months months, Rcd time portable months months, Rcd time fixed months months
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
8 na row
| Env | Equipment months | Rcd push portable months | Rcd push fixed months | Rcd time portable months | Rcd time fixed months |
|---|---|---|---|---|---|
| 1 | 6 | — | 6 | 12 | 12 |
| 2 | 12 | 3 | 6 | 12 | 12 |
| 3 | 60 | 3 | 6 | 24 | 24 |
| 4 | 24 | 6 | 6 | 24 | 24 |
| 5 | 6 | — | — | 6 | — |
| 6 | 3 | — | — | 3 | 12 |
| 7 | — | — | — | — | — |
| 8 | — | — | — | — | — |