AS/NZS 3012:2019

Table 1

Maximum cord and cable lengths for construction sites

The site cord length tool reads the length limit for the rated current and conductor size. Each row gives four figures: general or specific use, each as a single phase and a three phase length.

Verified: read against the printed standard, pages 24. Checked 1 Oct 2026.

Units: Rated current A A, Csa mm 2 mm2, General single M m, General three M m, Specific single M m, Specific three M m

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3012:2019 page

13 rows

Table 1, Maximum cord and cable lengths for construction sites
Rated current ACsa mm 2 (mm2)General single M (m)General three M (m)Specific single M (m)Specific three M (m)
10125501530
101.535702040
102.5601203570
10410020060120
151.525501530
152.540802550
154651304080
15610020060120
1510170340100200
202.530602040
204501003060
206751504590
201013026075150