Table 1, Maximum cord and cable lengths for construction sites
Rated current ACsa mm 2 (mm2)General single M (m)General three M (m)Specific single M (m)Specific three M (m)
10125501530
101.535702040
102.5601203570
10410020060120
151.525501530
152.540802550
154651304080
15610020060120
1510170340100200
202.530602040
204501003060
206751504590
201013026075150