AS/NZS 3008.1.1:2025
Table 3.34
Correction factors for single‑core circuits on trays, ladders, racks and cleats in air
On the 2025 edition, the cable size, correction factors and DC cable size tools read this table for single‑core circuits on a tray, a ladder, a rack or cleats. The values print the same as in 2017.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 74. تم التحقق في 27 Sept 2026.
الوحدات: Tiers count, Count circuits per tier or row
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
22 صفوف
| Item | Installation | Spacing | Tiers (count) | Factors |
|---|---|---|---|---|
| 1 | unperforated-trays | touching | 1 | 0.95, 0.85, 0.84 |
| 2 | unperforated-trays | touching | 2 | 0.92, 0.83, 0.79 |
| 3 | unperforated-trays | touching | 3 | 0.91, 0.82, 0.76 |
| 4 | perforated-trays | touching | 1 | 0.97, 0.89, 0.87 |
| 5 | perforated-trays | touching | 2 | 0.94, 0.85, 0.81 |
| 6 | perforated-trays | touching | 3 | 0.93, 0.84, 0.79 |
| 7 | ladder-supports-racks-cleats | touching | 1 | 1, 0.95, 0.94 |
| 8 | ladder-supports-racks-cleats | touching | 2 | 0.95, 0.9, 0.88 |
| 9 | ladder-supports-racks-cleats | touching | 3 | 0.95, 0.89, 0.85 |
| 10 | vertical-perforated-trays | touching | 1 | 0.94, 0.85, — |
| 11 | vertical-perforated-trays | touching | 2 | 0.92, 0.83, — |
| 12 | unperforated-trays | spaced | 1 | 0.95, 0.95, 0.94 |
| 13 | unperforated-trays | spaced | 2 | 0.92, 0.91, 0.87 |
| 14 | unperforated-trays | spaced | 3 | 0.91, 0.9, 0.85 |
| 15 | perforated-trays | spaced | 1 | 0.97, 0.97, 0.96 |
| 16 | perforated-trays | spaced | 2 | 0.94, 0.93, 0.89 |
| 17 | perforated-trays | spaced | 3 | 0.93, 0.92, 0.86 |
| 18 | ladder-supports | spaced | 1 | 1, 1, 1 |
| 19 | ladder-supports | spaced | 2 | 0.95, 0.95, 0.93 |
| 20 | ladder-supports | spaced | 3 | 0.95, 0.94, 0.9 |
| 21 | vertical-perforated-trays | spaced | 1 | 1, 0.91, 0.89 |
| 22 | vertical-perforated-trays | spaced | 2 | 1, 0.9, 0.86 |