Lumaktaw sa nilalaman
AmpSize

AS/NZS 3008.1.1:2017

Table 27(1), 27(2)

Rating factors for air and soil ambient temperature

The cable size and correction factors tools read the Australian ambient factor when the Standard is AU and the Edition is 2017. The factors sit on a 40 °C air base, so 40 °C on site applies no reduction.

Na-verify: binasa laban sa naka-print na standard, mga pahina 88. Na-check noong 24 Sept 2026.

Mga unit: Temp °C

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3008.1.1:2017

41 na row

Table 27(1), 27(2), Rating factors for air and soil ambient temperature
InsulationMediumConductor temp CTemp (°C)Factor
PVCair75151.35
PVCair75201.28
PVCair75251.21
PVCair75301.14
PVCair75351.07
PVCair75401
PVCair75450.91
PVCair75500.82
PVCair75550.72
PVCair75600.6
PVCair75650.49
PVCair75700.37
XLPEair90151.26
XLPEair90201.2
XLPEair90251.15
XLPEair90301.1
XLPEair90351.05
XLPEair90401
XLPEair90450.94
XLPEair90500.88
XLPEair90550.81
XLPEair90600.73
XLPEair90650.65
XLPEair90700.57
XLPEair90750.47
XLPEair90800.34
XLPEair90850.19
PVCsoil75101.14
PVCsoil75151.1
PVCsoil75201.05
PVCsoil75251
PVCsoil75300.95
PVCsoil75350.89
PVCsoil75400.83
XLPEsoil90101.11
XLPEsoil90151.07
XLPEsoil90201.03
XLPEsoil90251
XLPEsoil90300.97
XLPEsoil90350.93
XLPEsoil90400.89