AS/NZS 3000:2018

Table 3.8, 3.10

Aerial conductor clearances and spacing at supports

The aerial spans tool reads the minimum clearance for each conductor type from Table 3.8. From Table 3.10 it reads the conductor spacing at the supports for a span. Table 3.10 stops at a 60 m span. The tool refuses a longer span rather than hold the 60 m figure.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 206, 208. I tirohia 26 Sept 2026.

Ngā unit: Clearance m, Spacing m, Span m

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

7 rārangi

Table 3.8, 3.10, Aerial conductor clearances and spacing at supports
KindConductorOver areas used by vehiclesOver areas not used by vehiclesOver roofs used for traffic or resortOver other roofs and structuresHorizontal from wallsFrom clothes lines aerials or stay wiresFrom telecommunications linesAbove swimming poolsAbove sailing or irrigationMax span MInsulatedBare
clearancebare5.553.73221.2——
clearanceinsulated-unsheathed4.6332120.635.5
clearanceneutral-screened4.632.70.5120.634.5
spacing100.20.4
spacing250.30.5
spacing450.40.6
spacing600.50.7