Table 3.8, 3.10

Aerial conductor clearances and spacing at supports

The aerial spans tool reads the minimum clearance for each conductor type from Table 3.8. From Table 3.10 it reads the conductor spacing at the supports for a span. Table 3.10 stops at a 60 m span. The tool refuses a longer span rather than hold the 60 m figure.

Na-verify: binasa laban sa naka-print na standard, mga pahina 206, 208. Na-check noong 26 Sept 2026.

Mga unit: Clearance m, Spacing m, Span m

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3000:2018

7 na row

Table 3.8, 3.10, Aerial conductor clearances and spacing at supports
KindConductorOver areas used by vehiclesOver areas not used by vehiclesOver roofs used for traffic or resortOver other roofs and structuresHorizontal from wallsFrom clothes lines aerials or stay wiresFrom telecommunications linesAbove swimming poolsAbove sailing or irrigationMax span MInsulatedBare
clearancebare5.553.73221.2——
clearanceinsulated-unsheathed4.6332120.635.5
clearanceneutral-screened4.632.70.5120.634.5
spacing100.20.4
spacing250.30.5
spacing450.40.6
spacing600.50.7