AS/NZS 3000:2018
Cl 4.5.2.3, Figure 4.9 and Table 4.3
Recessed luminaire classes, where each may go, and the default clearances
The downlight clearance tool reads whether insulation may abut or cover each class, the classes each installation may take, and the default clearances for a lamp up to 100 W.
Verified: read against the printed standard, pages 230–233, 237–242 (PDF = page + 4). Checked 1 Oct 2026.
Units: Surface limit C C, Mounting limit C C, Value mm mm, Max lamp W W
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
22 rows
| Kind | Abutted | Covered | With insulation | Surface limit C | Mounting limit C | Clause | Page | Jurisdiction | Installation | Classes | As | Value mm | Max lamp W | Value W |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| class | no | no | no | — | 90 | Table 4.3 | 238 | |||||||
| class | no | no | yes | — | 90 | Table 4.3 | 238 | |||||||
| class | yes | no | yes | 90 | 90 | Table 4.3 | 239 | |||||||
| class | yes | no | yes | 135 | 90 | Table 4.3 | 240 | |||||||
| class | yes | yes | yes | 90 | 90 | Table 4.3 | 241 | |||||||
| class | yes | yes | yes | 90 | 90 | Table 4.3 | 241 | |||||||
| class | no | no | no | — | — | Table 4.3 | 242 | |||||||
| permitted | 4.5.2.3.5(a)(i) | 237 | au | residential | do-not-cover, ca90, ic, ic4 | |||||||||
| permitted | 4.5.2.3.5(a)(ii) | 237 | au | non‑residential | non‑ic, do-not-cover, ca90, ic, ic4 | |||||||||
| permitted | 4.5.2.3.5(b)(i) | 237 | nz | residential | ca90, ca135, ic, ic4 | |||||||||
| permitted | 4.5.2.3.5(b)(ii) | 237 | nz | non‑residential | non‑ic, do-not-cover, ca90, ca135, ic, ic4 | |||||||||
| legacy | 4.5.2.3.5 Exception (a) | 237 | ca90 | |||||||||||
| legacy | 4.5.2.3.5 Exception (b) | 237 | ca135 | |||||||||||
| legacy | 4.5.2.3.5 Exception (c) | 237 | ic | |||||||||||
| legacy | 4.5.2.3.5 Exception (d) | 237 | ic4 | |||||||||||
| clearance | Figure 4.9 | 231 | 100 | 100 | ||||||||||
| clearance | Figure 4.9 | 231 | 100 | 100 | ||||||||||
| clearance | Figure 4.9 | 231 | 100 | 100 | ||||||||||
| clearance | Figure 4.9 | 231 | 50 | 100 | ||||||||||
| rule | 4.5.2.3.2 | 232 | — | |||||||||||
| rule | 4.5.2.3.3(a)(viii) | 233 | 100 | |||||||||||
| rule | 4.5.2.3.3(a)(ii) | 232 | — |