Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3000:2018

Cl 4.5.2.3, Figure 4.9 and Table 4.3

Recessed luminaire classes, where each may go, and the default clearances

The downlight clearance tool reads whether insulation may abut or cover each class, the classes each installation may take, and the default clearances for a lamp up to 100 W.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 230–233, 237–242 (PDF = page + 4). I tirohia 1 Oct 2026.

Ngā unit: Surface limit C C, Mounting limit C C, Value mm mm, Max lamp W W

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

22 rārangi

Cl 4.5.2.3, Figure 4.9 and Table 4.3, Recessed luminaire classes, where each may go, and the default clearances
KindAbuttedCoveredWith insulationSurface limit CMounting limit CClausePageJurisdictionInstallationClassesAsValue mmMax lamp WValue W
classnonono—90Table 4.3238
classnonoyes—90Table 4.3238
classyesnoyes9090Table 4.3239
classyesnoyes13590Table 4.3240
classyesyesyes9090Table 4.3241
classyesyesyes9090Table 4.3241
classnonono——Table 4.3242
permitted4.5.2.3.5(a)(i)237auresidentialdo-not-cover, ca90, ic, ic4
permitted4.5.2.3.5(a)(ii)237aunon‑residentialnon‑ic, do-not-cover, ca90, ic, ic4
permitted4.5.2.3.5(b)(i)237nzresidentialca90, ca135, ic, ic4
permitted4.5.2.3.5(b)(ii)237nznon‑residentialnon‑ic, do-not-cover, ca90, ca135, ic, ic4
legacy4.5.2.3.5 Exception (a)237ca90
legacy4.5.2.3.5 Exception (b)237ca135
legacy4.5.2.3.5 Exception (c)237ic
legacy4.5.2.3.5 Exception (d)237ic4
clearanceFigure 4.9231100100
clearanceFigure 4.9231100100
clearanceFigure 4.9231100100
clearanceFigure 4.923150100
rule4.5.2.3.2232—
rule4.5.2.3.3(a)(viii)233100
rule4.5.2.3.3(a)(ii)232—