AS/NZS 3000:2018

Cl 4.5.2.3, Figure 4.9 and Table 4.3

Recessed luminaire classes, where each may go, and the default clearances

The downlight clearance tool reads whether insulation may abut or cover each class, the classes each installation may take, and the default clearances for a lamp up to 100 W.

已核验:对照印刷版标准阅读,页码 230–233, 237–242 (PDF = page + 4)。检查于 1 Oct 2026。

单位:Surface limit C C, Mounting limit C C, Value mm mm, Max lamp W W

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

22 行

Cl 4.5.2.3, Figure 4.9 and Table 4.3, Recessed luminaire classes, where each may go, and the default clearances
KindAbuttedCoveredWith insulationSurface limit CMounting limit CClausePageJurisdictionInstallationClassesAsValue mmMax lamp WValue W
classnonono—90Table 4.3238
classnonoyes—90Table 4.3238
classyesnoyes9090Table 4.3239
classyesnoyes13590Table 4.3240
classyesyesyes9090Table 4.3241
classyesyesyes9090Table 4.3241
classnonono——Table 4.3242
permitted4.5.2.3.5(a)(i)237auresidentialdo-not-cover, ca90, ic, ic4
permitted4.5.2.3.5(a)(ii)237aunon‑residentialnon‑ic, do-not-cover, ca90, ic, ic4
permitted4.5.2.3.5(b)(i)237nzresidentialca90, ca135, ic, ic4
permitted4.5.2.3.5(b)(ii)237nznon‑residentialnon‑ic, do-not-cover, ca90, ca135, ic, ic4
legacy4.5.2.3.5 Exception (a)237ca90
legacy4.5.2.3.5 Exception (b)237ca135
legacy4.5.2.3.5 Exception (c)237ic
legacy4.5.2.3.5 Exception (d)237ic4
clearanceFigure 4.9231100100
clearanceFigure 4.9231100100
clearanceFigure 4.9231100100
clearanceFigure 4.923150100
rule4.5.2.3.2232—
rule4.5.2.3.3(a)(viii)233100
rule4.5.2.3.3(a)(ii)232—