AS/NZS 3000:2018
Cl 3.5.2
Neutral conductor of a circuit
The neutral current tool reads the rules for the neutral of a multiphase circuit. It must be at least the largest active, with an Exception for a mostly multiphase load. The harmonics tool reads the 100 % share and the 40 % substantial load of Cl 3.5.2(b)(i).
Verified: read against the printed standard, pages 160–161 (PDF = page + 4). Checked 2 Oct 2026.
Units: Value percent
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
7 rows
| Kind | Value (percent) | Clause | Page |
|---|---|---|---|
| shall | — | 3.5.2(a) | 160 |
| shall | — | 3.5.2(b)(i) | 160-161 |
| value | 100 | 3.5.2(b)(i) | 161 |
| value | 40 | 3.5.2(b)(i) Note 1 | 161 |
| shall | — | 3.5.2(b)(ii) | 161 |
| exception | — | 3.5.2 Exception 2 | 161 |
| exception | — | 3.5.2 Exception 3 | 161 |