AS/NZS 5033:2021
AS/NZS 5033:2021 isolators, enclosures and earthing
PV array isolator, enclosure and earthing figures
The PV array tool reads the isolator ambient temperatures, the outdoor IP codes, the earthing sizes of Figure 4.13, the 0.5 ohm limit and the 120 V alarm threshold here.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 26, 37–39, 55, 65–67 (PDF 34, 45–47, 63, 73–75). تم التحقق في 1 Oct 2026.
الوحدات: Value per row
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
15 صفوف
| Clause | Value (per row) | Unit | Page |
|---|---|---|---|
| 4.3.4.2.3(a)(i) | 40 | °C | 38 |
| 4.3.4.2.3(a)(ii) | 40 | °C | 38 |
| 4.3.4.2.3(a)(iii) | 60 | °C | 38 |
| Table 4.5 | 56 | IP | 55 |
| 4.4.6.1 | 55 | IP | 55 |
| 4.4.6.2 | 300 | mm | 55 |
| Figure 4.13 | 35 | V | 66 |
| Figure 4.13 | 16 | mm² | 66 |
| Figure 4.13 | 4 | mm² | 66 |
| Figure 4.13 | 4 | mm² | 66 |
| Figure 4.13 | 4 | mm² | 66 |
| 4.6.5 | 0.5 | Ω | 65 |
| Table 4.6 | 120 | V | 67 |
| Table 4.6 | 1.5 | m | 67 |
| 3.5.3 | 120 | V | 26 |