Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3008.1.2:2017

Table 52, 53, 54, 55

Short-circuit K values and temperature limits

The fault rating tool reads the k factor for the conductor start temperature and the short-circuit temperature limit. The limit comes from the insulation class and the conductor size band, or from the joint in the run when the joint is the lower of the two.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 121–123 (PDF 125–127), with Table 1 on page 13. I tirohia 26 Sept 2026.

Ngā unit: K A*s^0.5/mm2, Initial temp C degC, Final temp C degC, Max size mm 2 mm2

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3008.1.2:2017

43 rārangi

Table 52, 53, 54, 55, Short-circuit K values and temperature limits
KindMaterialInitial temp C (degC)Final temp C (degC)K (A*s^0.5/mm2)Insulation classMax size mm 2 (mm2)Joint
kCu11014065.3
kCu11015074.9
kCu11016083.2
kCu110220119
kCu110250132
kCu110350164
kCu9014085.6
kCu9015093.1
kCu9016099.9
kCu90220131
kCu90250143
kCu90350173
kCu7514098.7
kCu75150105
kCu75160111
kCu75220140
kCu75250151
kCu75350180
kAl11014043.2
kAl11015049.5
kAl11016055
kAl11025087.1
kAl9014056.6
kAl9015061.5
kAl9016066
kAl9025094.5
kAl7514065.2
kAl7515069.6
kAl7516073.6
kAl7525099.9
insulation75160thermoplastic-75300
insulation75140thermoplastic-75
insulation90250cross-linked-90
insulation110250cross-linked-110
joint250exothermic-welded
joint160soldered
joint250compression
sheaththermoplastic200
sheathpolyethylene150
sheathhigh-density-polyethylene180
sheathpolychloroprene-or-csp200
sheathlead170
sheathlead-alloy200