AS/NZS 3000:2018

Cl 3.9.8

Segregation and separation of wiring systems

The segregation tool reads one row per case: what may share a pipe or cable, what needs segregation in a common enclosure, which voltage levels may mix, and the separation from gas, water and telecommunications services.

Verified: read against the printed standard, pages 181–184. Checked 27 Sept 2026.

Units: Separation mm mm

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

9 rows

Cl 3.9.8, Segregation and separation of wiring systems
CaseClausePermittedSeparation mmArrangementsExceptionsSwitchboard exception
different-installations3.9.8.2.1no———yes
different-occupancies3.9.8.2.1no———yes
common-enclosure3.9.8.2.2conditional50independently-sheathed-cables, fire-resisting-barrier, distance—yes
hv-with-lv-or-elv3.9.8.3no———no
lv-with-elv3.9.8.3conditional—double-insulation-equivalent, insulated-for-highest-voltage, separate-compartment—no
gas-or-water-above-ground3.9.8.4(b)conditional25—equipotential-bonding-conductor, heat-trace-cablingno
gas-or-water-underground3.9.8.4(b)pointer———no
telecommunications3.9.8.4(c)conditional50barrier, distance—no
telecommunications-shared-trench3.9.8.4(c)conditional50——no