AS/NZS 3000:2018

Cl 3.9.8

Segregation and separation of wiring systems

The segregation tool reads one row per case: what may share a pipe or cable, what needs segregation in a common enclosure, which voltage levels may mix, and the separation from gas, water and telecommunications services.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 181–184. I tirohia 27 Sept 2026.

Ngā unit: Separation mm mm

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

9 rārangi

Cl 3.9.8, Segregation and separation of wiring systems
CaseClausePermittedSeparation mmArrangementsExceptionsSwitchboard exception
different-installations3.9.8.2.1no———yes
different-occupancies3.9.8.2.1no———yes
common-enclosure3.9.8.2.2conditional50independently-sheathed-cables, fire-resisting-barrier, distance—yes
hv-with-lv-or-elv3.9.8.3no———no
lv-with-elv3.9.8.3conditional—double-insulation-equivalent, insulated-for-highest-voltage, separate-compartment—no
gas-or-water-above-ground3.9.8.4(b)conditional25—equipotential-bonding-conductor, heat-trace-cablingno
gas-or-water-underground3.9.8.4(b)pointer———no
telecommunications3.9.8.4(c)conditional50barrier, distance—no
telecommunications-shared-trench3.9.8.4(c)conditional50——no