Skip to content
AmpSize

AS/NZS 3000:2018

AS/NZS 3000:2018 IP codes by location

The least IP code AS/NZS 3000 names for a location, outside the Section 6 zones

The IP rating tool reads the least code the wiring rules name outside the wet area zones: enclosures, outdoor accessories, switchboards near hosing or sprinklers, saunas, hosed areas and an outdoor EV point.

Verified: read against the printed standard, pages 57, 140–143, 213–215, 355–356, 361, 570 (PDF 61, 144–147, 217–219, 359–360, 365, 574). Checked 1 Oct 2026.

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3000:2018 page

11 rows

AS/NZS 3000:2018 IP codes by location, The least IP code AS/NZS 3000 names for a location, outside the Section 6 zones
CodeCode orCode andForceClausePage
IP2XIPXXB—shall1.5.4.4(a)(i)57
IP4X——shall1.5.4.4(a)(ii)57
IP33——shall4.1.3214-215
IP23——shall4.1.3 Exception 1214
IPX6——shall2.10.2.5(g)141-142
IPX4——shall2.10.2.5(j) Exception (i)142
IP5X——note2.10.2.5(h) Note 1142
IP24IPX4B—shall6.5.4.1355
IPX5——shall6.7.4.1(a)361
IPX6——shall6.7.4.1(b)361
IPX4—IP4XshouldApp P Para P3.2.1 and P3.2.2570

Tools that read it (1)