AS/NZS 3000:2018
AS/NZS 3000:2018 IP codes by location
The least IP code AS/NZS 3000 names for a location, outside the Section 6 zones
The IP rating tool reads the least code the wiring rules name outside the wet area zones: enclosures, outdoor accessories, switchboards near hosing or sprinklers, saunas, hosed areas and an outdoor EV point.
Đã xác minh: đối chiếu với tiêu chuẩn in, trang 57, 140–143, 213–215, 355–356, 361, 570 (PDF 61, 144–147, 217–219, 359–360, 365, 574). Đã kiểm tra 1 Oct 2026.
Đây là các giá trị mà AmpSize mã hóa. Không sao chép nội dung tiêu chuẩn. Hãy đối chiếu với tiêu chuẩn hiện hành.
11 hàng
| Code | Code or | Code and | Force | Clause | Page |
|---|---|---|---|---|---|
| IP2X | IPXXB | — | shall | 1.5.4.4(a)(i) | 57 |
| IP4X | — | — | shall | 1.5.4.4(a)(ii) | 57 |
| IP33 | — | — | shall | 4.1.3 | 214-215 |
| IP23 | — | — | shall | 4.1.3 Exception 1 | 214 |
| IPX6 | — | — | shall | 2.10.2.5(g) | 141-142 |
| IPX4 | — | — | shall | 2.10.2.5(j) Exception (i) | 142 |
| IP5X | — | — | note | 2.10.2.5(h) Note 1 | 142 |
| IP24 | IPX4B | — | shall | 6.5.4.1 | 355 |
| IPX5 | — | — | shall | 6.7.4.1(a) | 361 |
| IPX6 | — | — | shall | 6.7.4.1(b) | 361 |
| IPX4 | — | IP4X | should | App P Para P3.2.1 and P3.2.2 | 570 |