Whakawhiti ki te ihirangi
AmpSize

AS/NZS 3000:2018

I1

Protective device ratings for imperial cables in alterations and repairs

The imperial cable tool reads the protective device rating Table I1 allows for an old imperial conductor, by wire count and wire diameter, installation method, insulation temperature rating and device type. The table is for alteration and repair work.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 540–541. I tirohia 26 Sept 2026.

Ngā unit: Rating A, Diameter in in

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

14 rārangi

I1, Protective device ratings for imperial cables in alterations and repairs
SizeWiresDiameter inMethodV 75 cbV 75 fuseV 60 cbV 60 fuse
1/.04410.044unenclosed1310108
1/.04410.044partially-surrounded10886
3/.02930.029unenclosed16121310
3/.02930.029partially-surrounded138106
3/.03630.036unenclosed20161610
3/.03630.036partially-surrounded1610108
1/.06410.064unenclosed20161612
1/.06410.064partially-surrounded1610138
7/.02970.029unenclosed32202516
7/.02970.029partially-surrounded20161612
7/.03670.036unenclosed40253220
7/.03670.036partially-surrounded25202016
7/.04470.044unenclosed50324025
7/.04470.044partially-surrounded32252520

Ngā taputapu e pānui ana i tērā (1)

Ngā aratohu me ngā whārangi ako e whakahua ana i tēnei (1)