Skip to content
AmpSize

AS/NZS 1680.1:2006

Table 3.1

Recommended maintained illuminances for various types of tasks, activities or interiors

The lighting lumen method tool reads the maintained illuminance for a class of task. It maps each workplace room use to one class, and names the table in its steps. The rows are workplace interiors. A house’s rooms, its kitchen and garage too, and outside areas are not in this table, so the tool marks their targets as typical.

Verified: read against the printed standard, pages 19 (PDF 21). Checked 1 Oct 2026.

Units: Lux lx

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 1680.1:2006 page

10 rows

Table 3.1, Recommended maintained illuminances for various types of tasks, activities or interiors
LabelLux (lx)Interiors
Movement and orientation40corridors, walkways
Rough intermittent80live storage of bulky materials, loading bays
Simple160entrance halls, automated process monitoring
Ordinary or moderately easy240food preparation, counters for transactions
Moderately difficult320routine office tasks
Moderately difficult400inspection of medium work
Difficult600drawing boards, proofreading
Very difficult800fine inspection
Extremely difficult1200graphic arts inspection
Exceptionally difficult1600watchmaking

Tools that read it (1)