EV charger circuit in a Victorian garage

EV charger circuit calculator

+4 references

Worked to AS/NZS 3000:2018 and AS/NZS 3008.1.1:2025 (AU). Tables checked 1 Oct 2026.

A drawn result card from the EV Charger tool: spare capacity short by 7 A.

A house in Victoria gets a wall charger in the garage. The charger draws 32 A. The board has a 63 A single‑phase supply. This guide checks whether the supply has room, and what cable the run needs.

The inputs

  • Australia, edition 2025. Mode 3 charger, one charger, single phase, 32 A.
  • Board supply 63 A, single phase.
  • Maximum demand without the charger: 38 A. The maximum demand tool gives this figure.
  • Run length 18 m, copper, PVC insulated, unenclosed and touching a surface.

The clause

AS/NZS 3000:2018 Cl 2.2.1.4 points to Appendix P for EV charging. Appendix P is informative. Its figures are guidance. Section 2 still applies to the final subcircuit.

Paragraph P2 sets the charger demand. The tool counts each charger at 100 % of its rated current on the heaviest phase. One 32 A charger counts as 32 A.

The steps

Open the run. The supply rating less the maximum demand leaves 25 A. The charger needs 32 A. The tool reports the board short by 7 A, and it marks the check as a fail.

The same run gives the Appendix P protection items. Paragraph P3.1 treats each connecting point as a dedicated circuit. Paragraph P4.1 asks for a 30 mA device, Type B, or Type A with d.c. fault detection. The d.c. trip level is 6 mA. Many chargers detect d.c. fault current themselves. Check the maker's data.

Close the gap

Two options remain. The first is a larger supply. With an 80 A supply, the tool shows 10 A left.

The second is load management. A device holds the charger to a set current. With a 25 A limit, the managed check shows 0 A left. It passes with no margin. The tool still reports the unmanaged check as a fail. The managed case relies on the device.

The cable

The tool sizes the cable at the charger rating, with the cable size tool's default inputs. It returns 4 mm², with a drop of 2.81 %. The default air temperature is 30 °C. A Victorian garage in summer runs hotter.

Run the cable size tool at 40 °C instead. At 40 °C the ambient factor is 1, and 4 mm² rates 29 A. It fails. The tool picks 6 mm², with a capacity of 37 A and a drop of 1.88 %.

At 30 °C the factor is 1.13. 4 mm² carries 32.77 A, a margin of only 0.77 A. Use the garage's real temperature.

Three phase and outdoors

A three‑phase charger changes less than it seems. Take a 32 A charger on each phase of a three‑phase board. The board has the same 63 A rating and 38 A demand. The tool still reports the heaviest phase short by 7 A.

If the charger mounts outdoors, Paragraph P3.2 gives the degree of protection as IPX4 and IP4X. Check the maker's data for the charger and its enclosure.

On the board

Fix the maximum demand first. An assessed figure from Table C1 is a design value. A measured figure on the heaviest phase can be lower. The result of this check depends on that one input, so state which one you used.

Load management does not remove the need for the cable to carry the charger rating. The cable here is sized at 32 A. Only the board check changes with the managed limit.

The result

CaseResult
63 A supply, 38 A demand, 32 A chargerShort by 7 A
80 A supply10 A left
63 A supply, 25 A load management0 A left
Cable at 30 °C4 mm², 32.77 A
Cable at 40 °C6 mm², 37 A

The charger does not fit the 63 A board unmanaged. Fix the supply or manage the load, then size the cable for the hottest garage day. Try it with these inputs.

This page is a design aid. Verify every value against the current edition of the standard.

See also: EV charging load and spare capacity, Maximum demand of an Australian house, Table C1 and Cable size for a 32 A circuit, Australia 2025.

Try it with these inputs

Charger supply
Single‑phase
Charger rated current
32 A
Number of chargers
1
Edition
AS/NZS 3008.1.1:2025
Insulation
PVC 75 °C
Country
Australia · Appendix P
Run length
18 m
Material
Copper
Maximum demand without the chargers
38 A
Installation method
Unenclosed touching
Charging mode
Mode 3
Board supply
Single‑phase
Main switch or supply rating
63 A
Open the calculator with these inputs

Where next

The ideas behind it

More worked examples

AmpSize is a design aid. Verify results against the current standard.

Was this useful?

A question, or a value that looks wrong? Contact us.