Te rahi UPS me te wā mahi pākahiko
Whakaritea te rahi o tētahi UPS me tōna pākahiko mō te wā mahi.
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Size a UPS for a comms rackThe UPS and battery to keep a comms rack and security system up for half an hour.
- Find the battery for an hour on UPSHow much battery an office rack needs to run for an hour.
- Size a UPS for a small data hallA three‑phase UPS for forty racks for ten minutes, and its input current.
- Pick a UPS for a home officeThe UPS for a computer and router to ride a short outage.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Ngā utanga i te UPS
- 3 rārangi
- Wātea mō te tipu
- 25 %
- Tauwhāinga pūngao puta UPS
- 0.9
- Wā rere i runga i te pākahiko
- 15 min
- Hiko pahi pātene
- 96 V
- Pai o te inverter i runga i te pākahiko
- 92 %
- Tauutu pakeke
- 1.25
- Wā whakaki anō
- 8 h
- Ngā wāhanga uru
- Wāhanga kotahi
- Uru hiko
- 230 V
- Whaihua UPS i te hiko matua
- 94 %
- Power factor o te whakauru
- 0.99
Te whakatau UPS, iti rawa
1.86kVA
- Te rahi noa
- 2 kVA
- Uta
- 1,340W
- Te kaha o te bateri
- 455Wh
- Te kaha o te bateri i te pahi
- 4.7Ah
- Te au whakauru
- 6.5A
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Utu, hiko pūmau1,340W
- Uta, apparent power1,424.6VA
- kVA mō te utaina me te mokowhiti 25 %1.78kVA
- kVA mō tōna kW i te power factor UPS 0.91.86kVA
- Te whakatau UPS, iti rawaHua1.86kVA
- Te rahi noa2 kVA
- Pūngao pātene mō te 15 meneti, me te pakeke455Wh
- Āheinga pātene i te 96 V4.7Ah
- Pūngao whakaurunga me te whakaki anō i roto i te 8 h1,488W
- Te au whakauru6.5A
Mō tēnei tātaitai
How this is calculated
A UPS has two sizes that matter: the power its inverter can deliver, and the energy its battery holds. This tool works both from a list of what the UPS supplies, then the current it draws from the supply.
You list each load with how many there are, the real power each draws in watts and its power factor. The tool adds the watts, and it adds each load's apparent power. With your headroom for growth on top, the UPS needs at least that many kVA, and its kW rating, its kVA times its output power factor, must cover the watts. The larger of the two is the rating. The tool also names the next typical size up; the sizes are common ratings, not a standard's list.
The battery must hold the load's watts for the run time, divided by the inverter's efficiency, times an ageing factor so it still lasts when old. Divided by the bus voltage that gives Ah, but at the run time's rate: a battery gives far less than its 10 or 20 hour Ah over a short run, so the maker's discharge table decides the battery.
The input is the load through the UPS's efficiency plus the power to recharge the battery in the time you set. AmpSize does not hold AS 62040, so the headroom, efficiencies and ageing factor are your assumptions. The result names the AS/NZS 3000 rules for converters.
| Step | Table or clause | What it decides |
|---|---|---|
| Load | Watts added, and each load's apparent power | The power the UPS supplies |
| Rating | The larger of the kVA and the kW at the output power factor | The UPS rating with headroom |
| Battery energy | Load times run time, over efficiency, times ageing | The energy at the battery bus |
| Battery capacity | Energy over the bus voltage, at the run time's rate | The Ah to look up in a maker's table |
| Input current | Load over efficiency, plus recharge | The current for the supply cable |
| Installation | AS/NZS 3000 Cl 4.12.4.2, Cl 4.12.5.1, Cl 4.12.5.2.2 and Cl 4.12.7 | The switch, protection, RCD and neutral rules |
Worked examples
- An office rack: two servers, three switches and storage, 15 min needs 1.86 kVA, so a 2 kVA unit, with 4.7 Ah at 96 V.
- The same rack for an hour still needs 1.86 kVA and a 2 kVA unit, but the battery holds 1,821 Wh.
- A comms rack and security system, 30 min on a 192 V battery needs 4.17 kVA, a 5 kVA unit, with 10.6 Ah at the bus.
- A small data hall of forty 1.2 kW racks, 10 min, three‑phase needs 61.86 kVA, an 80 kVA unit, drawing 76.6 A a phase.
- A home office PC and router, 10 min needs 0.51 kVA, so a 1 kVA unit.
Limits
The battery figure is the energy and Ah at the run time's rate. It does not pick cells: read the maker's constant-power discharge table at your end voltage and temperature. The tool does not model a UPS in parallel, redundancy such as N+1, the bypass supply, or a generator behind the UPS; for that, size the generator for the UPS's input.
See also: Generator sizing, Battery and Cable size.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
Me pēhea te rahi i tētahi UPS?
Tāpirihia ngā watts o ngā mea katoa e whangaia ana e ia, me ō rātou VA. Tāpirihia te mokowā mō te tupu. Me hipoki e te UPS kVA te VA, ā, me hipoki tōna reiti kW, te kVA whakareatia ki tōna power factor puta, ngā watts.
He pēhea te nui o te pākahiko e hiahiatia ana e au mō tētahi wā mahi?
Ko te pūngao he uta i ngā wāti ka whakareatia ki ngā hāora, ka wehea ki te efficiency o te inverter, ka whakareatia ki te ageing factor. Wehea ki te voltage bus mō te Ah, i te reiti wā rere, kātahi pānuitia te ripanga discharge a te kaihanga.
He aha te rerekē o te Ah i te tapanga pākahiko?
Ka hoatu te tapanga i te Ah i runga i ngā hāora 10, 20 rānei. I runga i ngā meneti 15 ka iti rawa atu tā taua pākahiko ano, nā reira ka kōwhiria te pākahiko UPS mai i te ripanga whakaheke constant-power, ehara i te tapanga.
He rahi taura pēhea e whāngai ana i tētahi UPS?
Whakaritea tōna rahi mō te iahiko whakauru: te uta kua wehea ki te efficiency o te UPS, me te power hei whakakī anō i te pākahiko. Ka hoatu e te taputapu taua iahiko hei kawe ki te taputapu Rahi Taura.
He aha te kī a AS/NZS 3000 mō tētahi UPS?
Ka uru a Cl 4.12 ki ngā kaiwhakarerekē, tae atu ki te UPS. Ka mau tonu te neutral ki te uta i te bypass, ka noho te whakamaru putanga i roto i te 15 m, ā, ka whati tētahi whakawhiti i te taha o ngā pākahiko i tā rātou puna.
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 4.12.4.2Switch for converter batteries
- AS/NZS 3000:2018 Cl 4.12.5.1Converter overcurrent protection
- AS/NZS 3000:2018 Cl 4.12.5.2.2RCDs on a converter output
- AS/NZS 3000:2018 Cl 4.12.7Neutral continuity through a UPS
- AS/NZS 3000:2018 Cl 4.12Electricity converters, including UPS
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 2 Oct 2026.