AmpSize

UPS size at battery run time

I-size ang UPS at ang battery nito para sa run time.

Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Mga load sa UPS
3 row
Headroom para sa paglaki
25 %
Output power factor ng UPS
0.9
Run time sa baterya
15 min
Voltage ng battery bus
96 V
Efficiency ng inverter sa baterya
92 %
Ageing factor
1.25
Recharge time
8 h
Input phases
Single phase
Input voltage
230 V
Efficiency ng UPS sa mains
94 %
Input power factor
0.99

Rating ng UPS, hindi bababa sa

1.86kVA

Karaniwang laki
2 kVA
Load
1,340W
Enerhiya ng baterya
455Wh
Kapasidad ng baterya sa bus
4.7Ah
Input current
6.5A

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Load, real power1,340W
  2. Load, apparent power1,424.6VA
  3. kVA para sa load na may 25 % headroom1.78kVA
  4. kVA para sa kW nito sa UPS power factor na 0.91.86kVA
  5. Rating ng UPS, hindi bababa saResulta1.86kVA
  6. Karaniwang laki2 kVA
  7. Energy ng baterya para sa 15 min, kasama ang ageing455Wh
  8. Kapasidad ng baterya sa 96 V4.7Ah
  9. Input power na may recharge sa loob ng 8 h1,488W
  10. Input current6.5A

Tungkol sa calculator na ito

How this is calculated

A UPS has two sizes that matter: the power its inverter can deliver, and the energy its battery holds. This tool works both from a list of what the UPS supplies, then the current it draws from the supply.

You list each load with how many there are, the real power each draws in watts and its power factor. The tool adds the watts, and it adds each load's apparent power. With your headroom for growth on top, the UPS needs at least that many kVA, and its kW rating, its kVA times its output power factor, must cover the watts. The larger of the two is the rating. The tool also names the next typical size up; the sizes are common ratings, not a standard's list.

The battery must hold the load's watts for the run time, divided by the inverter's efficiency, times an ageing factor so it still lasts when old. Divided by the bus voltage that gives Ah, but at the run time's rate: a battery gives far less than its 10 or 20 hour Ah over a short run, so the maker's discharge table decides the battery.

The input is the load through the UPS's efficiency plus the power to recharge the battery in the time you set. AmpSize does not hold AS 62040, so the headroom, efficiencies and ageing factor are your assumptions. The result names the AS/NZS 3000 rules for converters.

StepTable or clauseWhat it decides
LoadWatts added, and each load's apparent powerThe power the UPS supplies
RatingThe larger of the kVA and the kW at the output power factorThe UPS rating with headroom
Battery energyLoad times run time, over efficiency, times ageingThe energy at the battery bus
Battery capacityEnergy over the bus voltage, at the run time's rateThe Ah to look up in a maker's table
Input currentLoad over efficiency, plus rechargeThe current for the supply cable
InstallationAS/NZS 3000 Cl 4.12.4.2, Cl 4.12.5.1, Cl 4.12.5.2.2 and Cl 4.12.7The switch, protection, RCD and neutral rules

Worked examples

Limits

The battery figure is the energy and Ah at the run time's rate. It does not pick cells: read the maker's constant-power discharge table at your end voltage and temperature. The tool does not model a UPS in parallel, redundancy such as N+1, the bypass supply, or a generator behind the UPS; for that, size the generator for the UPS's input.

See also: Generator sizing, Battery and Cable size.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Paano ko i-size ang UPS?

Idagdag ang watts ng lahat ng sinusuplayan nito, at ang VA nito. Magdagdag ng headroom para sa paglaki. Dapat kayanin ng UPS kVA ang VA, at dapat kayanin ng kW rating nito, kVA na pinarami ng output power factor, ang watts.

Gaano karaming battery ang kailangan ko para sa run time?

Ang energy ay ang load sa watts na i-multiply sa oras, hinati sa inverter efficiency, at i-multiply sa ageing factor. Hatiin sa bus voltage para makuha ang Ah, sa run time rate, at pagkatapos basahin ang discharge table ng maker.

Bakit ganoon kalayo ang Ah sa label ng battery?

Ang label ay nagbibigay ng Ah sa 10 o 20 oras. Sa loob ng 15 minuto, mas kaunti na ang ibinibigay ng parehong battery, kaya ang UPS battery ay pinipili mula sa constant-power discharge table, hindi sa label.

Anong laki ng cable ang nagpapakain sa UPS?

I-size ito para sa input current: ang load na hinati sa efficiency ng UPS, dagdag ang power para i-recharge ang battery. Ibinibigay ng tool ang current na iyon para ipasok sa cable size tool.

Ano ang sinasabi ng AS/NZS 3000 tungkol sa UPS?

Sakop ng Cl 4.12 ang converters, kasama ang UPS. Nananatiling buo ang neutral papunta sa load sa pamamagitan ng bypass, ang output protection ay nasa loob ng 15 m, at ang switch sa tabi ng battery ang nagpuputol ng supply nito.

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 2 Oct 2026.