Three phase power calculator

I-convert sa pagitan ng power, current, voltage at power factor.

Walang standard

Mga input

Worked example gamit ang mga default na input.

Mga phase
Three phase
Voltage
400 V
Current
50 A
Power factor
0.9

Apparent power

34.64kVA

Real power
31.18kW
Reactive power
15.1kvar

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Apparent powerResulta34.64kVA
  2. Real power31.18kW
  3. Reactive power15.1kvar

Tungkol sa calculator na ito

How this is calculated

The tool converts between current, apparent power, real power and reactive power. It works on one phase or on three. It does not read a standard. The method is the power triangle.

  1. Inputs. You pick one phase or three. You enter the voltage, the current and the power factor. On three phases the voltage is the line voltage.
  2. Apparent power. On three phases, S = √3 × V × I ÷ 1000. On one phase, S = V × I ÷ 1000. The result is in kVA.
  3. Real power. P = S × power factor. The result is in kW.
  4. Reactive power. Q = √(S² − P²). The result is in kvar.

Enter the line voltage on three phases, such as 400 V. Enter the phase voltage on one phase, such as 230 V.

Worked example

Limits

The tool assumes a balanced load. It assumes a sine wave. A load with harmonics needs a true RMS reading. The tool does not size a cable or a device. Use the cable size calculator for that. A motor has efficiency as well as power factor. Use the motor tool for its full load current.

Use the tool to check a meter reading, a motor plate or a supply request. For a load in kW, the full load current tool works the other way. A low power factor raises the kVA for the same kW. The power factor correction tool finds the capacitor size.

See also: kVA to amps at 400 V, Current and power factor to kW and Power factor and reactive power.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng three phase power calculator?

Kino-convert ng tool ang voltage, current at power factor tungo sa apparent power, real power at reactive power. Gumagana ito sa isang phase o tatlong phase. Ang three phase na resulta ay gumagamit ng square root ng tatlo at ng line voltage.

Aling mga input ang pinakamahalaga?

Itinatakda ng voltage at current ang apparent power. Hinahati ng power factor ang apparent power na iyon tungo sa real power at reactive power. Ang power factor na 1 ay walang reactive power. Sa tatlong phase, ilagay ang line to line voltage, hindi ang phase to neutral voltage.

Ano ang mga karaniwang gotcha?

Kinakalkula ng tool ang reactive power mula sa magnitude. Kaya hindi nito ipinapakita kung leading o lagging ang load. Ipinapalagay ng resulta na pantay at balanse ang load ng tatlong phase. Nasa page address ang mga input, kaya muling nagagawa ng link ang parehong conversion.