Skip to content
AmpSize

Earthing and bonding calculator

Size earthing, main earth and bonding conductors.

AS/NZS 3000

Reads AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Try a job 6

Each job fills in example values. Replace them with your values.

Inputs

Worked example with the default inputs. The live calculator replaces it when the page loads.

Active conductor material
Copper
Largest active conductor
16 mm²
Consumer mains active conductor
16 mm²
Bonding case
General equipotential bonding
Check by calculation
No

Protective earthing conductor

6mm²

From the table
6mm²
Main earthing conductor
6mm²
Bonding conductor
4mm²

This result is a design aid. Verify it against the current standard.

Calculation steps

  1. Protective earthing conductor from the table6mm²

    AS/NZS 3000:2018 Table 5.1

  2. Main earthing conductor6mm²

    AS/NZS 3000:2018 Cl 5.3.3.2

  3. Bonding conductor4mm²

    AS/NZS 3000:2018 Cl 5.6.3.2

  4. Selected protective earthing conductorResult6mm²

    AS/NZS 3000:2018 Table 5.1

About this calculator

How this is calculated

The tool sizes the protective earthing conductor, the main earthing conductor and the bonding conductor. It reads AS/NZS 3000:2018. It starts from the size of the active conductor.

  1. Protective earthing conductor. You enter the active size and the conductor material. The tool reads the earth size from Table 5.1.
  2. Main earthing conductor. The tool reads Cl 5.3.3.2. It sizes the conductor from the consumer mains size you enter.
  3. Bonding conductor. You pick the bonding case. The tool reads the bonding conductor size from Cl 5.6.3.2.
  4. Adiabatic check. If you turn it on, you enter the fault current and clearing time. The tool then checks the selected conductor against the adiabatic equation. A larger size replaces the table size if it fails.
StepTable or clauseWhat it decides
Protective earthAS/NZS 3000:2018 Table 5.1The earth size for the active size
Main earthCl 5.3.3.2The main earthing conductor size
BondingCl 5.6.3.2The bonding conductor size

Worked example

  • 16 mm² copper active conductors. Consumer mains are also 16 mm², with the general bonding case. The protective earthing conductor is 6 mm². The main earthing conductor is 6 mm². The bonding conductor is 4 mm².

Limits

The table sizes cover the usual installation. The tool does not cover a special case. A long earth route can need a larger conductor for loop impedance. Use the loop impedance tool for that.

The tool does not choose the earth electrode or the earthing system. It does not check the conduit or cable support. The adiabatic check is off until you turn it on.

See also: The MEN system, Short-circuit withstand and the k factor and the fault rating tool.

Questions

Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.

What does the earthing tool do?

The tool reads the protective earthing conductor size for the largest active conductor. It reads the main earthing conductor size from the consumer mains. It applies the 4 mm² minimum and the 120 mm² maximum, and reports the bonding size. It can also check the size by calculation.

Which table gives the earthing conductor size?

AS/NZS 3000:2018 Table 5.1. The tool reads the copper active column or the aluminium active column. The main earthing conductor rule comes from Clause 5.3.3.2. The bonding sizes come from Clause 5.6.3.2.

How does the calculation option work?

It applies Equation 5.1 of Clause 5.3.3.1.3. The tool squares the fault current and multiplies by the disconnection time. It takes the square root of that and divides by K to get the area. It rounds the result up to the next standard size. The equation applies from 0.1 s to 5 s.

Which K value should I use?

Note 1 to Clause 5.3.3.1.3 gives 170 for bare copper. It gives 136 for PVC insulated copper not laid up in a cable with other conductors. An earthing conductor can be a core laid up in a cable with others. For that case, use the k factor from AS/NZS 3008.1.2 Table 52 instead.

What size is the MEN connection?

The tool sizes the main earthing conductor from the consumer mains active size. In copper, it is at least 4 mm², and it never needs to be larger than 120 mm². Aluminium active conductors below 16 mm² are not tabulated.

Clauses and tables this tool reads

Every clause and table, with how each was verified

Tables last checked on 27 Sept 2026.

Was this useful?

A question, or a value that looks wrong? Contact us.