Electrical wire colour guide
Find wire colours for fixed wiring and cords, old and new.
Reads AS/NZS 3000:2018 and AS/NZS 3760:2022. Tables checked 1 Oct 2026.
Try a job 4
Each job fills in example values. Replace them with your values.
- Find the wire colours for an AU houseActive, neutral and earth colours for Australian domestic wiring.
- Find out what a black wire isEvery function a black conductor can carry, and where.
- Read the colours of an older houseBare or green earths and yellow actives, and how to sleeve them.
- Check the cores of a three-phase cordPhase, neutral and earth cores of a five-core cord.
Inputs
Worked example with the default inputs. The live calculator replaces it when the page loads.
- Question
- What colour is each conductor
- Country
- New Zealand
- Wiring
- Fixed installation wiring
- Phases
- Single phase
- Installation
- Domestic
- Age
- Current colours
Active · neutral · earth
Red or brown · Black · Green/yellow
- Active, recommended
- Red or brown
- Neutral
- Black
- Protective earth
- Green/yellow
- Equipotential bonding
- Green/yellow
This result is a design aid. Verify it against the current standard.
Calculation steps
- Active, recommendedRed or brown
AS/NZS 3000:2018 Table 3.4 Note 2(a)
- NeutralBlack
AS/NZS 3000:2018 Table 3.4 Note 4
- Protective earthGreen/yellow
AS/NZS 3000:2018 Table 3.4
- Equipotential bondingGreen/yellow
AS/NZS 3000:2018 Table 3.4
- Active, permittedAny colour other than green, yellow, green/yellow, black or light blue
AS/NZS 3000:2018 Table 3.4
About this calculator
How this is calculated
The tool answers two questions. The first is what colour each conductor should be. The second is what a conductor of a given colour can be, when you find one on site.
For fixed installation wiring the tool reads the wiring rules' table of conductor colours. Protective earth and equipotential bonding conductors are green/yellow. A neutral is black or light blue, except in a New Zealand domestic installation, where it is black only. An active may be any colour other than green, yellow, green/yellow, black or light blue. The table's notes recommend red or brown for a single-phase active, and red, white or blue for the actives of a multiphase circuit. The tool shows those as recommendations, beside the rule.
An older installation may carry colours from a previous edition. A bare or green earthing or bonding conductor may stay, and so may a yellow live conductor. New terminations on them take sleeving: green/yellow on the earth, white on the yellow active.
For flexible cords the tool reads the in-service testing standard. Its colour table gives the international scheme and the superseded one, which older and imported cord sets still use. A second table gives the cores of each modern cord, single phase or three phase, Class I or Class II, with or without a neutral.
To identify a colour, the tool checks every row of both standards and lists each function the colour can carry, and where.
| Step | Table or clause | What it decides |
|---|---|---|
| Earth, bonding and neutral | Table 3.4 | The colour of each function in fixed wiring |
| Recommended actives | Table 3.4 Note 2 | Red or brown, or red, white and blue |
| New Zealand domestic neutral | Table 3.4 Note 4 | Black only |
| Older earths and actives | Cl 3.8.2.2 and Cl 3.8.2.3 | What may stay, and the sleeve at a new termination |
| Cord colours, current and superseded | AS/NZS 3760 Table C.1.1 | The active, neutral and earth of a cord |
| Cord cores | AS/NZS 3760 Table C.1.2 | The cores of each modern cord |
Worked examples
- A New Zealand house. The recommended active is red or brown, the neutral black, and the protective earth and bonding green/yellow.
- An Australian three-phase board. The recommended actives are red, white or blue, the neutral black or light blue, and the earth and bonding green/yellow.
- A five-core cord. The phases are brown, black and grey, the neutral blue, and the earth green/yellow.
- A yellow conductor in an older house. It can only be an active from a previous edition. Treat it as live and sleeve it white at a new termination.
- A black conductor on site. Neutral or active: a neutral in fixed wiring and in a superseded cord, a phase in a modern three-phase cord.
Limits
A colour says what a conductor should be, not what it is: prove it by test before work. The tool does not cover the special applications of Cl 3.8.3, such as numbered cores, or the internal wiring of equipment. It does not set a phase order for red, white and blue, because the table sets none.
See also: Wire colours in NZ and Australia, old and new, Reading the wiring in an older house and Test and Tag.
Questions
Each answer describes what this tool calculates. The result is a design aid. Verify against the current standard.
What colour is the neutral wire in New Zealand?
Black in a domestic installation: AS/NZS 3000 Table 3.4 Note 4 allows no other colour there. Outside a domestic installation, and in Australia, a neutral may be black or light blue.
What colour is the active wire?
Any colour other than green, yellow, green/yellow, black or light blue. Red or brown is recommended for a single-phase active, and red, white or blue for the actives of a multiphase circuit.
What are the old wire colours?
An older installation may have a bare or green earth and yellow live conductors. They may stay, but a new termination on them takes green/yellow or white sleeving. Old flexible cords used red, black and green.
What are the colours in a flexible cord?
Brown for the active, light blue for the neutral and green/yellow for the earth. A three-phase cord has brown, black and grey phases, with a blue neutral where it has one.
Can I mix European and NZ or AU colours?
Not in one enclosure or one multicore cable, by Table 3.4 Note 3. Brown and grey cores beside red, white and blue ones make the phases hard to read.
Clauses and tables this tool reads
- AS/NZS 3000:2018 Cl 3.8.2.1Conductor identification by sleeving
- AS/NZS 3000:2018 Cl 3.8.2.2Older earthing and bonding conductors
- AS/NZS 3000:2018 Cl 3.8.2.3Older yellow live conductors
- AS/NZS 3000:2018 Table 3.4Conductor colours for installation wiring, and the rules for older and sleeved conductors
- AS/NZS 3760:2022 Tables C.1.1 and C.1.2Conductor colours of flexible cords, international and superseded
Every clause and table, with how each was verified
Tables last checked on 1 Oct 2026.
Related tools
- Test and tag intervalsRetest intervals and pass limits for portable gear.AS/NZS 3760
- Test results checkerCheck measured test results against Section 8 limits.AS/NZS 3000AS/NZS 3017Electricity (Safety) Regulations 2010
- IP rating chart and decoderDecode an IP code and find the least for a location.AS 60529AS/NZS 3000