IEEE 1584-2018

Tables 8 and 10

Typical bus gaps, enclosure sizes and working distances by equipment class

The arc flash tool reads the typical gap, box size and working distance for the equipment when you leave them blank.

Verified: read against the printed standard, pages 37, 40 (PDF 38, 41). Checked 1 Oct 2026.

Units: Gap mm mm, Height mm mm, Width mm mm, Depth mm mm, Working distance mm mm

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the IEEE 1584-2018 page

9 rows

Tables 8 and 10, Typical bus gaps, enclosure sizes and working distances by equipment class
LabelGap mmHeight mmWidth mmDepth mmWorking distance mm
15 kV switchgear1521143762762914.4
15 kV MCC152914.4914.4914.4914.4
5 kV switchgear104914.4914.4914.4914.4
5 kV switchgear (tall)1041143762762914.4
5 kV MCC104660.4660.4660.4914.4
Low-voltage switchgear32508508508609.6
Shallow low-voltage MCC or panelboard25355.6304.8203.2457.2
Deep low-voltage MCC or panelboard25355.6304.8—457.2
Cable junction box13355.6304.8203.2457.2