IEEE 1584-2018
Tables 8 and 10
Typical bus gaps, enclosure sizes and working distances by equipment class
The arc flash tool reads the typical gap, box size and working distance for the equipment when you leave them blank.
Verified: read against the printed standard, pages 37, 40 (PDF 38, 41). Checked 1 Oct 2026.
Units: Gap mm mm, Height mm mm, Width mm mm, Depth mm mm, Working distance mm mm
These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.
9 rows
| Label | Gap mm | Height mm | Width mm | Depth mm | Working distance mm |
|---|---|---|---|---|---|
| 15 kV switchgear | 152 | 1143 | 762 | 762 | 914.4 |
| 15 kV MCC | 152 | 914.4 | 914.4 | 914.4 | 914.4 |
| 5 kV switchgear | 104 | 914.4 | 914.4 | 914.4 | 914.4 |
| 5 kV switchgear (tall) | 104 | 1143 | 762 | 762 | 914.4 |
| 5 kV MCC | 104 | 660.4 | 660.4 | 660.4 | 914.4 |
| Low-voltage switchgear | 32 | 508 | 508 | 508 | 609.6 |
| Shallow low-voltage MCC or panelboard | 25 | 355.6 | 304.8 | 203.2 | 457.2 |
| Deep low-voltage MCC or panelboard | 25 | 355.6 | 304.8 | — | 457.2 |
| Cable junction box | 13 | 355.6 | 304.8 | 203.2 | 457.2 |