IEEE 1584-2018
Tables 8 and 10
Typical bus gaps, enclosure sizes and working distances by equipment class
The arc flash tool reads the typical gap, box size and working distance for the equipment when you leave them blank.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 37, 40 (PDF 38, 41). تم التحقق في 1 Oct 2026.
الوحدات: Gap mm mm, Height mm mm, Width mm mm, Depth mm mm, Working distance mm mm
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
9 صفوف
| Label | Gap mm | Height mm | Width mm | Depth mm | Working distance mm |
|---|---|---|---|---|---|
| 15 kV switchgear | 152 | 1143 | 762 | 762 | 914.4 |
| 15 kV MCC | 152 | 914.4 | 914.4 | 914.4 | 914.4 |
| 5 kV switchgear | 104 | 914.4 | 914.4 | 914.4 | 914.4 |
| 5 kV switchgear (tall) | 104 | 1143 | 762 | 762 | 914.4 |
| 5 kV MCC | 104 | 660.4 | 660.4 | 660.4 | 914.4 |
| Low-voltage switchgear | 32 | 508 | 508 | 508 | 609.6 |
| Shallow low-voltage MCC or panelboard | 25 | 355.6 | 304.8 | 203.2 | 457.2 |
| Deep low-voltage MCC or panelboard | 25 | 355.6 | 304.8 | — | 457.2 |
| Cable junction box | 13 | 355.6 | 304.8 | 203.2 | 457.2 |