IEC 60255-151:2009 / IEEE C37.112-2018

Table 1 / IEEE C37.112 Table 1

IDMT overcurrent curve constants

The IDMT tool reads the three constants that shape each named relay curve.

Verified: read against the printed standard, pages 29 (PDF 31), Annex A Table A.1. Checked 26 Sept 2026.

Units: K -, Alpha -, C -

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the IEC 60255-151:2009 / IEEE C37.112-2018 page

7 rows

Table 1 / IEEE C37.112 Table 1, IDMT overcurrent curve constants
NameK (-)Alpha (-)C (-)
IEC-SI0.140.020
IEC-VI13.510
IEC-EI8020
IEC-LTI12010
IEEE-MI0.05150.020.114
IEEE-VI19.6120.491
IEEE-EI28.220.1217