IEC 60255-151:2009 / IEEE C37.112-2018
Table 1 / IEEE C37.112 Table 1
IDMT overcurrent curve constants
The IDMT tool reads the three constants that shape each named relay curve.
Na-verify: binasa laban sa naka-print na standard, mga pahina 29 (PDF 31), Annex A Table A.1. Na-check noong 26 Sept 2026.
Mga unit: K -, Alpha -, C -
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
Bumalik sa card nito sa page ng IEC 60255-151:2009 / IEEE C37.112-2018
7 na row
| Name | K (-) | Alpha (-) | C (-) |
|---|---|---|---|
| IEC-SI | 0.14 | 0.02 | 0 |
| IEC-VI | 13.5 | 1 | 0 |
| IEC-EI | 80 | 2 | 0 |
| IEC-LTI | 120 | 1 | 0 |
| IEEE-MI | 0.0515 | 0.02 | 0.114 |
| IEEE-VI | 19.61 | 2 | 0.491 |
| IEEE-EI | 28.2 | 2 | 0.1217 |