Current ratings (d.c.), 2‑core cable, thermoplastic 75 °C

The DC cable size tool reads the d.c. rating here for one 2‑core thermoplastic cable, in copper or aluminium, for each installation method.

Verified: read against the printed standard, pages 60–61. Checked 27 Sept 2026.

Units: Rating A

These are the values AmpSize encodes. No text of the standard is reproduced. Verify against the current standard.

Back to its card on the AS/NZS 3008.1.1:2025 page

19 rows

Table 3.24, Current ratings (d.c.), 2-core cable, thermoplastic 75 °C
SizeUnenclosed spacedUnenclosed touchingUnenclosed sunEnclosed airInsulation partialInsulation partial enclosedInsulation completeInsulation complete enclosedBuried directUnderground enclosureAl unenclosed touchingAl unenclosed spacedAl unenclosed sunAl enclosed airAl insulation partialAl insulation partial enclosedAl insulation completeAl insulation complete enclosedAl buried directAl underground enclosure
1151411131110762619——————————
1.5191814161413983324——————————
2.527262023201913124634——————————
437342730272417156045——————————
646443439353122207556——————————
10646046524842302610175——————————
16858060686454403413298626647524942312610275
25113107799085725345170128838862706656413513299
3513913197112105906556205154101108758781705143159119
50170159116133128107——244185124132901039983——189144
70215202145170161136——300228156167112132125105——233177
95265249176205199164——361280193205136159154127——280217
120308289202241231193——411319224239157187179150——319248
150352330228272264218——462366255273177211204168——358284
185406380260315304252——524416295315202245236196——406323
240484453304369362295——611492351375236286281229——473381
300560523347434418347——694570404433268336323269——537441
400654610398500488400——798655473507309388378310——618508
500757706454593565475——909768548588352460438368——705595